Section 8.0 HMI Maintenance
HGA IOM
104
8.0 HMI Maintenance
Clock Battery Replacement
The HMI Display Real Time Clock is maintained by a non-rechargeable battery internal to the
HMI Display. Change the battery every ten years or as needed. The system will continue to
function as an active filter with a dead battery, but HMI information (fault logs and trend plots) will
not be maintained between power cycles.
To replace the battery, open the battery cover on the back of the HMI Display and remove the old
battery. Dispose or recycle the old battery in accordance with any applicable national,
state/provincial, and local requirements. Install new battery and close battery cover.
Replacement Battery Type: 3V Lithium CR2032 x Quantity 1
Figure 58: HMI Display Battery Location
Software Field Upgrades
In the event the HMI Display application software needs to be upgraded, the USB host port on the
back panel of the HMI Display can be used for field upgrades. Software upgrade instructions will
be sent with any software updates provided by TCI.
Figure 59: HMI Display USB Host Location
Back View of HMI Display
Battery
Cover
Back View of HMI Display
USB Host
Port for
Software
Upgrades