Section 7.0 HMI Introduction
HGA IOM
94
Figure 51: Tech Setup Screen
Table 35: Tech Setup Screen Elements
Screen Element
Description
Operation Modes
Takes user to “Operation Mode Setup” screen. This screen is outlined below
Password Setup
This button is password protected. Takes user to pop-up screen where passwords
can be re-configured.
Run/Stop Control Setup
Takes user to “Run/Stop Control Setup” sub screen. Outline to follow.
Load Settings
This button will restore the user saved settings from non-volatile persistent
memory. A confirmation screen will pop up asking “Are you sure you want to load
saved settings”. If “Yes” is chosen, any temporary changes made to the working
set point parameters will be lost and the user saved settings will be restored. If
“No” is pressed, the user will be sent back at the “Basic Setup” screen.
Save Settings
This button will save the current working settings to non-volatile memory that
persist when power is removed from the unit. To save the current settings, choose
“Yes” on the confirmation screen, or choose “No” to cancel and go back to the
“Basic Setup”. The settings will not be saved if “No” is chosen.
.
Tech Setup +
The password protected Tech Setup + button opens application specific setup
screens for advanced configuration of the active filter. Access to this HMI screen is
not needed for basic system installation and commissioning. If a specialized setup
feature is required for your application, an authorized TCI field service
representative will provide instruction on those features.
Full Load Amps Entry
This button allows user to enter in the system full load amps rating and is used to
calculate the ITDD display shown on the “Line Status” screen
Note:
ITDD Display is not available for load side configured units