Section 6.0 Filter Operation
HGA IOM
52
Table 15: Active Filter 100kAIC Circuit Breaker Manufacturer Part Number and Trip Ratings.
HGA Unit Rating*
ABB - Option 2000
Allen Bradley - Option 5000
Eaton - Option 7000
LSIS - 0300
480VAC
600VAC***
Amps**
MFG P/N
Amps**
MFG P/N
Amps**
MFG P/N
Amps**
MFG P/N
45A 50A
39A
80A
XT2LQ3080BFF000XXX
100A
140G-H0F3-D10
100A
EGC3100FFG
N/A
N/A
90A 100A
78A
125A
XT2LU3125BFF000XXX
125A
140G-H0F3-D12
125A
EGC3125FFG
N/A
N/A
150A
110A
150A
XT4LQ3175BFF000XXX
175A
140G-J0F3-D17
175A
JGC3175FAG
N/A
N/A
200A
150A
225A
XT4LQ3225BFF000XXX
225A
140G-J0F3-D22
225A
JGC3225FAG
N/A
N/A
250A
185A
300A
T5LQ300TW
300A
140G-K0F3-D30
300A
LGC3300FAG
N/A
N/A
300A
220A
400A
T5LQ400TW
400A
140G-K0H3-D40
350A
LGC3350FAG
N/A
N/A
350A
260A
400A
T5LQ400TW
400A
140G-K0H3-D40
500A
LGC3500FAG
N/A
N/A
400A
300A
N/A
N/A
N/A
N/A
600A
LGC3600FAG
N/A
N/A
500A
370A
N/A
N/A
N/A
N/A
600A
LGC3600FAG
N/A
N/A
600A
450A
N/A
N/A
N/A
N/A
N/A
N/A
630A
UTS800LT NG0 630A
3P LL UL
700A
520A
N/A
N/A
N/A
N/A
N/A
N/A
800A
UTS800LT NG0 800A
3P LL UL
*The HGA Active Filter controls have a current limit that limits the filter output current to the amp rating of the active
filter.
**Amps listed are maximum values for the circuit breaker. Actual trip setpoints may vary.
***For 600 V units the breaker is located on the 480 V secondary of the included 600 V/480 V K-Rated
Autotransformer.
****Trip setpoints should be set following manufacturer instructions.
Table 16: Active Filter 65kAIC Circuit Breaker Manufacturer Part Number and Trip Ratings.
HGA Unit Rating*
ABB - Option 0100
Allen Bradley - Option 4000
Eaton - Option 6000
LSIS - 0200
480VAC
600VAC***
Amps**
MFG P/N
Amps**
MFG P/N
Amps**
MFG P/N
Amps**
MFG P/N
45A 50A
39A
80A
XT2HQ3080BFF000XXX
100A
140G-G6C3-D10
100A
EGH3100FFG
N/A
N/A
90A 100A
78A
125A
XT2HU3125BFF000XXX
125A
140G-H6F3-D12
125A
EGH3125FFG
N/A
N/A
150A
110A
150A
XT4HQ3175BFF000XXX
175A
140G-J6F3-D17
175A
JGH3175FAG
N/A
N/A
200A
150A
225A
XT4HQ3225BFF000XXX
225A
140G-J6F3-D22
225A
JGH3225FAG
N/A
N/A
250A
185A
300A
T5HQ300TW
300A
140G-K6F3-D30
300A
LGH3300FAG
N/A
N/A
300A
220A
400A
T5HQ400TW
400A
140G-K6H3-D40
350A
LGH3350FAG
N/A
N/A
350A
260A
400A
T5HQ400TW
400A
140G-K6H3-D40
500A
LGH3500FAG
N/A
N/A
400A
300A
N/A
N/A
N/A
N/A
600A
LGH3600FAG
N/A
N/A
500A
370A
N/A
N/A
N/A
N/A
600A
LGH3600FAG
N/A
N/A
600A
450A
N/A
N/A
N/A
N/A
N/A
N/A
630A
UTS800HT NG0 630A
3P LL UL
700A
520A
N/A
N/A
N/A
N/A
N/A
N/A
800A
UTS800HT NG0 800A
3P LL UL
*The HGA Active Filter controls have a current limit that limits the filter output current to the amp rating of the active
filter.
**Amps listed are maximum values for the circuit breaker. Actual trip setpoints may vary.
***For 600 V units the breaker is located on the 480 V secondary of the included 600 V/480 V K-Rated
Autotransformer.
****Trip setpoints should be set following manufacturer instructions.