Section 7.0 HMI Introduction
HGA IOM
65
Table 17: Power & Communications Terminals
Terminal
Pin
Description
Label
Rating
J1
1
HMI Display
For factory use
N/A
J2
1
RS485
Not Connected
N/A
2
B
3
Ground
4
A
5
Not connected
J3
1
Input Power
Neutral
120 VAC
2
Line
J4
1-14
Micro Programming
For factory use
N/A
J19
1
HMI Power Supply
24 VDC
24 VDC
2
Common
3
Not Connected
J22
1
Start Command
24 VDC
Contact Closure
2
Start
Note
: The power terminal on the back of the HMI display accepts 28 to 14 AWG stranded wire, with
a tightening torque of 4.4 in-lb. (0.5 Nm).
Table 18: Form C Relay Contacts
Terminal
Pin
Description
Label
Tightening Torque
Wire Range
J5
1
Run
Normally Closed
4.4 lbs.-in (0.5 Nm)
28-14 Awg
2
Common
3
Normally Open
J6
1
Power On
Normally Closed
4.4 lbs.-in (0.5 Nm)
28-14 Awg
2
Common
3
Normally Open
J7
1
Fault
Normally Closed
4.4 lbs.-in (0.5 Nm)
28-14 Awg
2
Common
3
Normally Open
J12
1
Current Limit
Normally Closed
4.4 lbs.-in (0.5 Nm)
28-14 Awg
2
Common
3
Normally Open
Note
: Form-C relay contacts are gold plated with a load rating of 2.0A @ 250VAC.
HMI Display Connections
Note
: The following section describes the default ModbusRTU network connection available on
the base model. If an optional advanced network Communications Gateway is included in the
Interface Module, see the appendix for the specific Communications Gateway configuration.
The HMI display implements a ModbusRTU slave device over RS-485. This network connection
is available on the COM2/3 DB9 connector on the back of the HMI Display (see Figure 32).
The output registers from the HarmonicGuard
®
Active filter are mapped to Modbus register
address 40500. The input registers to the HarmonicGuard
®
Active filter are mapped to Modbus
register address 40564. For definitions of the input and output data available via the network
connection see tables below.
If the optional network Communications Gateway is present, the integrated ModbusRTU interface
on the HMI Display will not be available. When configured, the Communications Gateway will
occupy the ModbusRTU COM2/3 DB9 connector on the back of the HMI Display.