7C-FIN - Control Board Analog Input Status
L3
7D-FAUX - Option Board Analog Input Status
The integer value found at this parameter represents the real world value of the analog speed input at the
control board (7C-FIN) or from the option board input (7D-FAUX). It translates to a number in the range of
0-32,767 for 0 to maximum input.
7E-LIM - Analog Torque Limit Input Status
L3
The integer value found at this parameter represents the real world value of the analog torque limit input at
the control board. It translates to a number in the range of 0-15,000 for 0 to 150% of rated torque.
91-SIOC - SIO Communication BAUD Rate
L3
The integer value stored at this parameter determines the communication BAUD rate used between the
inverter and the host computer. Also, communication rights may be selected as either read/write or read-
only. Data codes "0" thru "3" provide both read and write capability. Codes “4” through “7” are read-only.
The BAUD rates available are:
48
Parameter
Units
Level
7A-CIN - Control Board Terminal Status
L3
7B-CIN2 - Option Board Terminal Status
The binary word represented by this integer value can be used to determine the status of the input terminal
function. Parameter 7A-CIN relates to the control board inputs, parameter 7B relates to the option board
inputs. The functions detected by this parameter are represented as active bits according to the following:
BIT #
FUNCTIONAL INDICATION
7
Will indicate that Reverse is active.
6
Will indicate that Forward is active.
5
Will indicate that R/J is active.
4
Will indicate that CTS function is active.
3
Will indicate that the ART input is active.
2
Will indicate that terminal PS3 is active.
1
Will indicate that terminal PS2 is active.
0
Will indicate that terminal PS1 is active.
DATA CODE
BAUD Rate
0/4
9600
1/5
4800
2/6
2400
3/7
1200
92-SIOA - SIO Slave Address
L3
This parameter allows an individual slave address to be assigned to each slave inverter in a multi-drive
application. Integer values between 1 and 94 are available.
93-SIOT - SIO Watchdog Timer
L3
This parameter is the storage location for a real number of seconds. With 93-SIOT set to a value greater
than zero, SIO activity must be logged at least once in that timeframe. It is used to monitor communication
integrity primarily.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for WFC1000 Series
Page 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 5: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 77: ...69 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 80: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...