4
Model Series
WFC1000
WFC2000
WFC4000
Programming Levels
Level 1 – Operator
Level 2 – Engineer
25, 43
Level 3 – Engineer with SIO
Parameter Block 00
Model #, software revision, rated current, heat
–
Drive Data
sink temp. trip point, mfg. serial #, repair
date code, & fault log.
Parameter Block 10
Output frequency, voltage, motor current, motor load,
–
Status
torque, drive temperature, elapsed time since power
applied, & total hours of operation.
Parameter Block 20
Definition of the LOCal/REMote keypad button in
–
Control
reference to the keypad, terminal strip, & the SIO link.
Also, various speed and torque references are
contained within this block.
Parameter Block 30
Various speed setpoints of the inverter.
–
Frequencies
Parameter Block 40
Ramp time selections (the time from start
–
Ramps
to maximum frequency FMAX or
from FMAX to stop)
Parameter Block 50
V/Hz curves, boost, minimum frequency at
–
Voltage/Frequency
full voltage, & skip frequencies.
Characteristics
Parameter Block 60
Torque limit setpoints, slip compensation, overload
–
Torque Limit
trip point, & auto-restart parameters.
Parameter Block 70
METer output, open collector output, &
–
I/O Definition
fault relay definitions.
Parameter Block 80
Storage & Retrieval of standard or custom programs,
–
Program Options
complete reset to factory settings, auto-restart, line
start lockout, PWM selection, display of engineering
units, alternate display languages, & customer
access code storage.
Parameter Block 90
BAUD or communication rate, slave address, watch-
–
RS485 Serial Link Options
dog timer, & retrieval of SIO generated fault codes.
Parameter Block A0
Speed Ratio & various parameters relative to the
–
Option Parameters
calibration of WPC option cards
Parameter Block B0
Option Board Identification and various parameters
–
Option Parameters
relative to the calibration of WPC option cards
Parameter Block C0
Used with program sequencer to
35
Event Control Bytes
control drive operation
Parameter Block E0
Used with program sequencer to
35
Event Count Bytes
control drive operation
Chassis, NEMA 1, NEMA 4
NEMA 4 standard thru 50/60 HP
–
Chassis/NEMA 1
In separate enclosure protected from dust,
7
moisture and corrosive fumes.
NEMA 1
Indoor protected from dust, moisture and corrosive fumes
7, 17
NEMA 4
Indoor protected from direct sunlight
7, 17
Operating Temperature
Chassis – 0° C to 50° C
NEMA 1/4 – 0° C to 40° C
–
Storage Temperature
-20° C to +60° C
–
Humidity
90% RH or less, noncondensing (chassis controls)
–
Vibration
0.6 G Maximum
–
Elevation
Less than 3,300 feet without derating
–
See
Page
Programming
Construction
Mounting
Location
Ambient
Conditions
TABLE 1.4 (Con’t.)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for WFC1000 Series
Page 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 5: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 77: ...69 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 80: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...