2.4 Inverter Watt Loss
The operation of the inverter generates heat
due to inefficiencies within the system. This
heat must be accounted for when mounting
the inverter within another enclosure. The
following table shows the watts generated by
the inverter when at full current and at
various switching frequencies. For specific
switching frequencies, use worst case
scenarios or consult the factory.
2.5 Line Fuse or Circuit Breaker Sizing
The user must provide either a circuit
breaker or a fused disconnect switch in
accordance with the National Electric
Code or Canadian Electrical Code and all
local codes. The following rules should
be used to select the correct size of the
input line fuses or circuit breaker.
A. Sizing/Fuse Type
The WFC
HT
Inverter is able to withstand
a 150% overload for 60 seconds.
For maximum protection of the inverter,
use the fuses listed in Table 2.5.
Recommended suppliers are Bussman
for 230 VAC, and for 460 VAC installa-
tions. Equivalent values from other man-
ufacturers may be substituted.
2.6 Wiring Practices
A. Applicable Codes
Care should be taken to insure that
field wiring is installed in accor-
dance with the National Electric
Code (NEC) or Canadian Electrical
Code (CEC) as a minimum stan-
dard. Where local codes exceed
these requirements, they must be
followed.
All WFC
HT
models are Underwriters
Laboratories Inc. (UL
®
) and
Canadian Underwriters Labora-
tories (cUL
®
) listed, and therefore
comply with the requirements of
NEC or CEC. Installations intended
to meet UL
®
requirements must
follow the instructions provided
herein. Refer to the WFC
HT
tech-
nical data plate and the motor
nameplate for electrical data.
WFC20007xHT
3.1
16kHz
58
131
WFC20010xHT
4
16kHz
72
163
WFC20020xHT
7.5
16kHz
121
273
WFC20030xHT
10.6
8kHz
161
238
WFC20050xHT
16.7
8kHz
216
320
WFC20075xHT
24.2
16kHz
299
671
WFC20100xHT
30.8
16kHz
402
902
WFC20150xHT
48.2
16kHz
603
1353
WFC20200xHT
59.4
16kHz
712
1598
WFC20250xHT
74.8
16kHz
1005
2256
WFC40010xHT
2.2
16kHz
62
140
WFC40020xHT
4.1
16kHz
99
222
WFC40030xHT
6.1
16kHz
114
256
WFC40050xHT
9.9
8kHz
181
267
WFC40075xHT
14.3
16kHz
255
573
WFC40100xHT
19.8
16kHz
350
785
WFC40150xHT
26.4
16kHz
468
1051
WFC40200xHT
33
8kHz
608
900
WFC40250xHT
42.9
16kHz
752
1688
WFC40300xHT
49.5
16kHz
864
1940
WFC40400xHT
67.1
4kHz
1152
1253
WFC40500xHT
82.5
4kHz
1439
1566
WFC40600xHT
98
4kHz
1727
1879
WFC40750xHT
121
2.5kHz
2223
2223
Max. Switching
Watt Loss
Watt Loss
Model
Amp
Frequency at
Default
at
Highest
Number
Rating
at Max. Amp
Switching
Switching
13
Model
Fuse
Model
Fuse
WFC4001-0
KTK-4 or KTK-R-4
WFC4002-0
KTK-7 or KTK-R-7
WFC4003-0
KTK-10 or KTK-R-10
WFC4005-0
KTK-15 or KTK-R-15
WFC4007-5
KTK-25 or KTK-R-25
WFC4010-0
KTK-35
WFC4015-0
KTK-50
WFC4020-0
JKS-60
WFC4025-0
JKS-100
WFC4030-0
JKS-100
WFC4040-0
JKS-125
WFC4050-0
JKS-175
WFC4060-0
JKS-200
WFC4075-0
JKS-200
TABLE 2.5
WFC1001-0
KTK-10 or KTK-R-10
WFC2000-7
KTK-5 or KTK-R-5
WFC2001-0
KTK-7 or KTK-R-7
WFC2002-0
KTK-15 or KTK-R-15
WFC2003-0
KTK-25 or KTK-R-25
WFC2005-0
KTK-30 or KTK-R-30
WFC2007-5
KTK-50
WFC2010-0
KTK-50
WFC2015-0
JKS-75
WFC2020-0
JKS-100
WFC2025-0
JKS-125
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for WFC1000 Series
Page 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 5: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 77: ...69 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 80: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...