49
95-SIOP - SIO Protocol
L3
The integer value stored at this parameter defines the communication protocol, selecting various ISO1745
and OPTO22
TM
options. The selections are outlined as follows:
OPTO22
TM
is a trademark of OPTO 22, Huntingdon Beach, CA.
Parameter
Units
Level
94-SIOF - SIO Fault Byte
L3
The integer value stored at this location may be decoded to a binary word to detect faults associated with
SIO communication. When various bits become active, they represent various faults that are SIO
communication related. The significant bits and their indication are as follows:
BIT #
FUNCTIONAL INDICATION
7
The value written in the last communication was outside the range of acceptable values.
6
The last communication was to a write protected parameter.
5
The last communication was to an unknown parameter.
1
The value in seconds programmed at 93-SIOT has been exceeded without a valid SIO
communication.
0
The restart procedure of drive re-initialization is in process.
DATA CODE
DESCRIPTION
0
ISO1745 protocol with even parity and seven data bits.
1
ISO1745 protocol with no parity and seven data bits.
2/3
OPTO
TM
protocol with no parity and seven data bits
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for WFC1000 Series
Page 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 5: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 77: ...69 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Page 80: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...