Coral FlexiCom 6000 Installation Manual
Hardware Installation Procedure
2-1
Si
te Inspection
2
2.1
Site Inspection
The Coral must be installed in a room with adequate space requirements as well as in
the correct environment. The Coral system requirements are described below.
1.
Verify that there is sufficient space for the Coral system cabinet(s). The
cabinet(s) require 3 feet (1 meter) clear space in front and in back of the
cabinet. The cabinets (main and expansion) are sold as 3 shelf units or 4 shelf
units.
describes the Cabinet Dimensions and Clear space
requirements for the different cabinet types.
Table 2-1
Cabinet
Dimensions and Clear
Space
2.
Verify that there is sufficient space for the Main Distribution Frame (MDF) in
addition to the space required by the cabinet. The MDF should be located
immediately adjacent to the Coral cabinet. The bottom of the MDF should be
no lower than 2 feet (61cm) and the top should be no higher than 6 feet (1.9
...................................................................................................
1
Space Requirements
DC Electrical Requirements on page 2-5
.
Coral System
Cabinet
Cabinet Dimensions
Clear Space
Requirements
Width
Height
Depth Left, Right
& Top
Front & Rear
3 Shelf Cabinet
35 in.
(89 cm)
60 in.
(153 cm)
21 in.
(53 cm)
6 in.
(16 cm)
36 in.
(100 cm)
4 Shelf Cabinet
35 in.
(89 cm)
74 in.
(188 cm)
21 in.
(53 cm)
6 in.
(16 cm)
36 in.
(100 cm)