Software Installation Procedure
Coral FlexiCom 6000 Installation Manual
S
ystem Diag
nostics
4
The technician may request a display of the current Faulty Objects Alarms for any of
the above fields by entering its field number from this branch. See
Diagnostic Alarms
in Chapter 22 of the relevant
Program Interface & Database Reference Manual
for
further details.
If the system contains no alarms when the technician requested an alarm report, the
No Active Alarms
message is displayed.
15-
CONTROLS
SAU* PHYSICAL CHECK
SAU* SOFTWARE CHECK
SAU* MISMATCH
These messages indicate a problem with the SAU
device, either the SAU is physically missing, or the
software is incompatible with the defined system or the
SAUs on both systems sides are not identical.
Fan Fault
Indicates that one of the fans or fan fuses is faulty and
must be replaced, see
Determining the Fan Fault and Replacing
.
Minor
PS-ATS 1/2/3
Details which PS-ATS is faulty. Either one of the PS-ATS
fuses must be replaced or the unit itself, see PS-ATS
Minor
LOW BATTERY ON 32GC
LOW BATTERY ON XMM UP
LOW BATTERY ON XMM DOWN
Details which battery needs replacement, see
Lithium Battery Test on page 3-16
.
Minor
CNT1 FAULT
The CNT1 clock mechanism located on the active 32GC
is faulty. Replace the 32GC card.
Minor
Faulty Objects
Alarms
PI Alarm Text and
Description
Major
or
Minor
Alarm