FAAST 7100X
INSTALLATION AND MAINTENANCE INSTRUCTIONS
© Pertronic Industries Ltd
20
FAAST XS (7100X) Installation Guide Iss 1.0, 201606
Section D : CONFIGURING Pertronic Fire Alarm Panels
A. Analogue Addressable F100 / F120:
7100X Stand-Alone
Type:
the 7100X Stand-Alone detector provides clean-contact relay outputs - these generally connect to
Loop Addressable Input Modules (eg M500MB or similar) to connect to an F100 / F120 panel
- all activation relays are configured as TYPE = SW (Module)
- generally the FIRE 1 relay will be configured to activate the Fire (F100) or Brigade (F120) relay,
though the FIRE 2 relay may be configured to activate the Fire (F100) or Brigade (F120) relay
where two Local Alarm level actions are required
- as many Activation Levels (1–3) as required may be used, since each uses a separate Input
Module.
Sensitivity: the FAAST 7100X detector Threshold Levels are configured at the detector :
Configuration \ Sensor
- three Activations Levels are available: ALERT, FIRE 1 and FIRE2
- each level provides individual Threshold Levels (sensitivity) for Day, Night and Weekend use
B. Conventional F16e / F4 / Loop Responder (NZS4512:2010):
7100X Stand-Alone
Sensitivity: the FAAST 7100X detector Threshold Levels are configured at the detector :
Configuration \ Sensor
- three
Activations Levels
are available:
ALERT
,
FIRE 1
and
FIRE2
- each level provides individual Threshold Levels (sensitivity) for
Day
,
Night
and
Weekend
use
- clean-contact relay outputs are provided for each Activation Threshold - these connect to one or
more individual circuits, depending upon the number of Activation Levels required
FIRE 1
terminate with a 10K EOL resistor to Normalise the circuit
(or FIRE 2): - switch a 470R resistor to activate as a Smoke Alarm or switch a 180R resistor to activate as a
Heat Alarm
- generally the FAAST
FIRE 1
relay will be configured to activate the panel’s
Fire
relay, though the
FIRE 2
relay may activate the
Fire
relay
ALERT:
terminate with a 10K EOL resistor to Normalise the circuit
- switch a 470R resistor to activate as a Smoke Alarm
- FIRE 1 and ALERT may be combined on a single circuit on the F16e provided the circuit is
configured for Residential mode and the 7100X FIRE 1 relay switches the 180R resistor (Heat
Alarm) and the ALERT switches the 470R resistor (Smoke Alarm)
DEFECT
switch a 1K8 resistor or an open or short-circuit to activate a Defect.
C. Conventional F16e / F16 (with FW=v8.0) / F4 / Loop Responder (NZS4512:1997):
7100X Stand-Alone
Sensitivity: the FAAST 7100X detector Threshold Levels are configured at the detector :
Configuration \ Sensor
- three
Activations Levels
are available:
ALERT
,
FIRE 1
and
FIRE2
- each level provides individual Threshold Levels (sensitivity) for
Day
,
Night
and
Weekend
use
- clean-contact relay outputs are provided for each Activation Threshold - these connect to one or
more individual circuits, depending upon the number of Activation Levels required
FIRE 1
terminate with a 10K EOL resistor to Normalise the circuit
(or FIRE 2): - switch a 470R resistor to activate as a Smoke Alarm or switch a 180R resistor or open-circuit to
activate as a Heat Alarm
- generally the FAAST
FIRE 1
relay will be configured to activate the panel’s
Fire
relay, though the
FIRE 2
relay may activate the
Fire
relay
ALERT:
terminate with a 10K EOL resistor to Normalise the circuit
- switch a 470R resistor to activate as a Smoke Alarm
- FIRE 1 and ALERT may be combined on a single circuit on the F16 provided the circuit is
configured for Apartment mode and the 7100X FIRE 1 relay switches the 180R resistor or open-
circuit (Heat Alarm) and the ALERT switches the 470R resistor (Smoke Alarm)
DEFECT switch a 1K8 resistor or a short-circuit to activate a Defect.
F16
functionality of a FAAST detector with an F16 is limited because of the restrictions of the F16 in
Apartment mode
BELL
Link
FIRE
Link
Apartment
Mode
Bell
Relay
Brigade
Relay
Fire
LED
Zone
LED
Latch Clear
In Out
Smoke
Yes No No Yes Yes
Ext
BCO
Reset
Heat
Yes Yes Yes Yes Yes