FAAST 7100X
INSTALLATION AND MAINTENANCE INSTRUCTIONS
© Pertronic Industries Ltd
17
FAAST XS (7100X) Installation Guide Iss 1.0, 201606
B. Design:
The following screen shots illustrate how to set the Hole Sensitivity from the Calculation window in Design
Setting Hole Sensitivity:
design the required pipe layout to meet the system layout requirements
select the
Calculation
icon
(i) select
Set Hole Sensitivity
(ii) set the Target Sensitivity for each of the activation levels: Alert; Fire 1 and Fire2
- the Target Sensitivity represents the sensitivity at the Sampling Point and equates to the sensitivity
of a point detector, eg. an OPT detector
- typical
Target Sensitivity
levels may be:
-
-
-
press the arrow to convert each
Target Sensitivity
to
Threshold
, then
OK
to accept
- this is the value used by
Threshold Values (%/m)
in
Configuration \ Sensor
Activation Level
VEWFD
EWFD
SFD
Alert
0.1 0.3 1.5
Fire 1
2.5 3 6
Fire 2
3 4.5 8