FAAST 7100X
INSTALLATION AND MAINTENANCE INSTRUCTIONS
© Pertronic Industries Ltd
16
FAAST XS (7100X) Installation Guide Iss 1.0, 201606
e) User Interface:
(i) Function
Lockout:
sets the Passcode to
make the buttons available at the user
interface
- default Passcode is 1111
(ii) Lockout Configuration Menus:
-
Device Configuration:
controls the
ability to select
4 Configuration
options
at the LCD Display
-
LCD Controls:
controls the ability to
select
7 LCD Setting
options at the LCD
Display
-
Functions:
controls the ability to select
3 Functions
options at the LCD Display
(iii) Graphics Display:
-
Language:
16 languages are available for the graphics display – default is English (English)
(iv) Sounder:
-
Fault Tone:
select Off, Pulsed or Continuous
-
Alarm Tone:
select Off, Pulsed or Continuous
f) ModBus
(i) ModBus:
determines the ModBus operating
mode
- TCP: ethernet based
- RS485: serial based, RTU or ASCII
based as required
(ii) Passcode:
sets the Passcode to unlock the
buttons on the device user interface
- default Passcode is
1111
(iii) Address:
sets the address for the TCP port
- default Address is
1
(iv) Baud Rate, Data Bits, Stop Bits, Parity
- define RS485 Serial port settings for the
ModBus client
g) Restore Default Values:
select to restore all
configuration parameters with Default values
h) Reset Baseline:
establishes an Air-Flow
baseline for the detector, displaying the true
measured Air-Flow status.