FAAST 7100X
INSTALLATION AND MAINTENANCE INSTRUCTIONS
© Pertronic Industries Ltd
15
FAAST XS (7100X) Installation Guide Iss 1.0, 201606
c) Network:
(i) Passwords:
FAAST XS devices have two types of
password
:
-
Web Access Password
:
required to
access remote monitoring available via a
web browser
-
the default
Password
is
1234
-
Administrator Password
- required to
reconfigure FAAST devices using PipeIQ
software
-
the default
Password
is
password
Caution:
if a Default Password is changed
and then lost, there may be a delay before
Pertronic can identify the password so that it
can be accessed or changed
(ii) Device Mail Server Configuration:
-
Sender Account
:
enter the email ID for the
Sender Account
-
SMTP Server Name:
enter the
SMTP Server Name
to use for email communication
-
SMTP Port
: default Port = 25
- contact the site IT department to confirm the correct Port
(iv) Device Connection:
select an IP Address automatically via DHCP or use a Static IP Address:
- Obtain an IP Address automatically via DHCP
- contact the site IT department to obtain the information required to connect to the site’s ethernet
- Use a Static IP Address:
- IP Address:
Default = 192.168.1.10
- Subnet Mask:
Default = 255.255.255.0
- Default Gateway:
Default = 192.168.1.1
- DNS Server: Primary and Secondary - contact the site IT department to obtain the information required
(v) Email
Notification:
- enter the Email addresses of the Users to whom to send the Alarm notifications. Email addresses may be
a Group of addresses
- select the notifications each user should receive using the check boxes
d) AirFlow
(i) Flow
Boundary:
specifies the set limit for
the AirFlow
- applicable settings are 0 to +/-50%
- Default setting is +/-20%
- Note:
(ii) Flow
Delay:
specifies the time set for the Air
Flow Defect
- applicable settings are 0 to 255 seconds
- default setting is 120 seconds
(iii) Fan Speed:
select the required fan speed :
High, Medium or Low as configured in
Design