Section IV
Multiple Unit Configuration
006-0006885 08/14/18
Rev H
27 of 48
MINV-4000-1U-28 Guide www.synqor.com
Three MINV units with AC OUTPUTs Paralleled
For three MINV units having their outputs connected in expanded parallel or redundant parallel,
the wiring diagram for the AC OUTPUT cables and the CONFIGURATION cable is shown below:
L1
N
PEGND
CONFIGURATION cable SYN-9343
AC OUTPUT
AC OUTPUT
AC OUTPUT
L1
N
PEGND
L1
N
PEGND
L1 N
TO LOAD
PEGND
When ordering, select the “F: Floating” or “R: AC Output Electronic Breaker” option for MINV
units configured in this manner.
If the user is providing the AC OUTPUT cable, the cable sections shown above in either blue or
in red should have the following minimum wire size, depending on whether the AC OUTPUT of
the MINV units is 115 Vac or 230 Vac.
MINV AC Output Voltage
Blue Cable Section
Minimum Wire Size
Red Cable Section Minimum
Wire Size
115 Vac
#8AWG (10 mm
2
)
#0AWG (65 mm
2
)
230 Vac
#10AWG (6 mm
2
)
#4AWG (26 mm
2
)