![Svantek SVAN 979 User Manual Download Page 172](http://html.mh-extra.com/html/svantek/svan-979/svan-979_user-manual_1409285172.webp)
172
SVAN 979 User Manual
Multifunction I/O
Screen that enables configuring the instrument's I/O port
parameters: I/
O Mode, Direct, D/A, Function, Slope
,
Polarisation, Active Level, Source, Source Type, Alarm
Level, Send SMS
and
Send E-Mail
.
Detailed description of the I/O port is given in
Appendix C.
Chapter
Appendix C
I/O Mode
Mode of the I/O port:
Analog Out
,
Digital In
,
Digital Out
.
Chapter
Appendix C
Analog Out
Mode of the I/O port when analogue signal is transmitted
from the input of the instrument to its output (pin 1 of the
I/O
connector) without any digital processing (
Direct
) or
after digital-to-analogue converter (
D/A
).
Chapter
Appendix C
Direct
Parameter that enables the measured signal from the
measurement channel to be transmitted to the pin 1 of
the
I/O
connector without any digital processing (filtering
and gaining).
Chapter
Appendix C
D/A
Parameter that enables transmitting the analogue signal
from the internal signal generator of the instrument after
digital-to-analogue converter to the pin 1 of the
I/O
connector, and the analogue input signal to the pin 2 of
the
I/O
connector after digital-to-analogue converter.
The input signal can be weighted with
HP, Z, A, C
or
B
filter (
Source
) and additionally gained by
-60 dB
to
60 dB
(
Gain
).
Chapter
Appendix C
Digital In
Mode of the I/O port when external digital signal is used
as an external trigger to start measurements. The
instrument is acting in this case as so called “slave
instru
ment”.
Chapter
Appendix C
Slope
Trigger voltage slope defined for the
Digital In
I/O mode:
[+] (uprising as default) or [
–] (falling).
Chapter
Appendix C
Digital Out
Mode of the I/O port when digital signal is used for
triggering other “slave instrument(s)” (the instrument is
acting in this case as a “master instrument”), or as a
source of alarm signal.
Chapter
Appendix C
Function
Functionality of the
Digital Out
I/O mode:
Trigger Pulse
or
Alarm Pulse
.
Chapter
Appendix C
Summary of Contents for SVAN 979
Page 272: ...272 SVAN 979 User Manual Appendixes 400 Hz 500 Hz 630 Hz 800 Hz 1000 Hz 1250 Hz ...
Page 273: ...273 SVAN 979 User Manual Appendixes 1600 Hz 2000 Hz 2240 Hz 2500 Hz 2800 Hz 3150 Hz ...
Page 274: ...274 SVAN 979 User Manual Appendixes 3550 Hz 4000 Hz 4500 Hz 5000 Hz 5600 Hz 6300 Hz ...
Page 275: ...275 SVAN 979 User Manual Appendixes 7100 Hz 8000 Hz 8500 Hz 9000 Hz 9500 Hz 10000 Hz ...
Page 312: ...312 SVAN 979 User Manual Appendixes Summary curve ...
Page 348: ...348 SVAN 979 User Manual Appendixes 250 Hz 315 Hz 400 Hz 500 Hz 630 Hz 800 Hz ...
Page 349: ...349 SVAN 979 User Manual Appendixes 1000 Hz 1250 Hz 1600 Hz 2000 Hz 2240 Hz 2500 Hz ...
Page 350: ...350 SVAN 979 User Manual Appendixes 2800 Hz 3150 Hz 3550 Hz 4000 Hz 4500 Hz 5000 Hz ...
Page 351: ...351 SVAN 979 User Manual Appendixes 5600 Hz 6300 Hz 7100 Hz 8000 Hz 8500 Hz 9000 Hz ...
Page 352: ...352 SVAN 979 User Manual Appendixes 9500 Hz 10000 Hz 10600 Hz 11200 Hz 11800 Hz 12500 Hz ...
Page 370: ...370 SVAN 979 User Manual Appendixes O ring gasket locations inside ...