
10.9
ALARM INFEED – INFEED MOTOR – INVERTER FAULT
Reset the inverter by clicking on the lit
blue Reset button below on the screen.
When the Inverter is reset the blue reset
button goes out.
Follow the instructions on the screen:
-
Inspection of the in-conveyor is needed.
-
Problem can be caused by food waste material getting stuck in the in-conveyor.
-
Clean the infeed hopper and the in-conveyor.
-
If necessary run the in-conveyor in reverse and thereby loosen any material that is stuck inside the
pipe leading to the cylinder.
-
Problem can also be caused by a faulty inverter.
Note that this ALARM needs to be acknowledged in the ALARM list in order to turn off the Alarm
Indicator which is visible in the left hand upper corner on all screens.
Use the ALARM button to go to alarm log menu.
From this alarm screen, it is possible to navigate to
the ‘manual run infeed’ screen pressing the symbol
with the infeed and two arrows on the alarm
screens.
Use the back and forward arrow trying to loosen the
blockage in the inconveyor.
Normally if there is a blockage of the infeed, the alarm that goes off is the ‘ALARM infeed - In-conveyor has
automatically reversed 2 times but is still unable to run’ see 10.8. If there is an alarm that the inverter for the
infeed motor has tripped the settings of the function of the infeed reversing two times may need adjusting,
see above.
If the infeed hopper, propellers and in-conveyor have been cleared and the alarm comes back
contact service personnel.
If the inverter trips repeatedly – contact service personnel.