32
PROGRAMMING MODE 23
[001]
Installer’s Code
It is strongly recommended that the factory programmed Installer’s Code be reprogrammed when the control panel
is installed. The default Installer’s Code is [8000].
WARNING: Do not enter [0000].
NOTE:
It is suggested that the Installer’s Code be programmed with alphanumeric characters (letters A to F) to
ensure that an Access Code could not inadvertently duplicate the Installer’s Code. The Installer’s Code
should be different from any other Access Code on the system.
[002] - [050]
For Future Use
[051] - [057]
Zone Configuration for Zones 1 - 7
Zones 1 through 7 can be configured as one of three options:
Option
Configuration
0
Normally Closed Zones
1
Normally Open Zones
2
End-of-Line Resistor Zones
• As each Address is entered, enter [0], [1] or [2]. The default setting for all zones is [0] Normally Closed. If a value
greater than 2 is entered, the system will program the value as “0”.
• Zone 8 is a Normally Closed Zone and cannot be changed.
• Trouble status for Zones 1 through 7 will only be active if these zones are programmed as End-of-Line Resistor
Zones.
WARNING: Changing the zone configuration may create false alarms due to different interpretations of alarm,
trouble and normal conditions. If is strongly recommended that the zone configuration be changed and then
completely tested with the system disconnected from the central station.
[058] - [400]
For Future Use
[401] - [408]
Individual Bypass Report Codes
Individual bypass report codes should only be programmed if the following two options are OFF:
• Common Bypass Report, Mode 22 Address [002] Light 4
• Calculate Bypass Report, Mode 22 Address [008] Light 1
If either of these options are “on”, do not program individual bypass report codes. If these options are “off”,
program 2-digit bypass reporting codes at Addresses [401] through [408].
Note that trouble zones have the same bypass feature as their alarm zones; trouble zones cannot be individually
bypassed.