31
Programming Mode 22
[033]
Printer Set-up
A serial printer can be connected to Programmable Output 1 only. The data transfer rate can be set at 300, 600,
1200, 2400 or 4800 baud.
Program as:
for baud rate of:
01
300
02
600
03
1200
04
2400 (default)
05
4800
NOTE: After changing the Printer Set-up, exit the programming mode and remove all power from the
system. After all power has been removed from the system, restore power to the system following
the Power-up Procedure instructions in the Installation section of this manual.
[034]
For Future Use
[035] - [037]
Programmable Output Types
Program a 2-digit Output Type in each Address from [035] through [037].
[038] - [062]
For Future Use
[063]
Language Selection for Printer
This Address is used to select the language in which all messages are printed to the printer.
01
1st Language (English)
02
2nd Language (French)
[064]
For Future Use
[065]
Maximum Alarm Reports per Zone per Armed Period
The number of alarms a zone can generate within an armed period can be limited. This feature is designed to
prevent repetitive alarm transmissions to the monitoring station from a zone that may have a mechanical or
electrical problem, or from zones that are repetitively tripped inadvertently.
The zones can be limited to 1 to 14 alarms per armed period, or the zones can be allowed to generate an unlimited
number of alarms. Program Address [065] with a hex number from 01 to 0E to allow 1 to 14 alarms per armed
period, or program Address [065] with 0F to allow for an unlimited number of alarms per armed period.
The counter for the number of alarms is reset when the control panel is armed or disarmed.
NOTE: Whenever the value at Address [065] is changed, the control panel must be armed and then disarmed in
order for the changes to be accepted by the system.