30
4
Opening Report on Alarm
This function will only operate when Open/Close Report in Mode 22 Address [001] is not selected.
When “on”, the system will send an opening report if an alarm occurred during the armed period.
5
Reserved
6
Auto-Arm Squawk
When “on”, the bell/siren will sound a short tone every 10 seconds during the Auto-Arm Exit Delay.
7
Open/Close Report by Group
This function will only operate when Open/Close Report is selected in Mode 22 Address [001].
When “on”, the system will report both Group and User information when reporting opening and closing events.
When “off”, the system will only report User information when reporting opening and closing events. This
option need not be selected when the system uses only one Group.
This option does not affect the reports printed on a local printer. When reports are printed on a local printer,
Group information will always be printed in the system has more than one Group.
8
Reserved
Address 008: System Options
Light
1
Calculate Bypass Report Code
When “on”, the bypass reporting code for a zone is based on the zone’s alarm reporting code programmed in
Mode 20 Addresses [301] through [308]. When “on”, bypass reports will be printed at the central station as:
---- BypZnXX where XX is the zone’s alarm code
When “off”, the bypass reporting code for a zone is taken from the codes programmed in Mode 23 Addresses
[401] through [408]. When “off”, bypass reports will be printed at the central station as:
Optn1 AlmZnXX where XX is the bypass code programmed in Mode 23
Note that trouble zones have the same bypass feature as their alarm zones; trouble zones cannot be
individually bypassed.
2
Reserved
3
Reserved
4
Reserved
5
Reserved
6
Reserved
7
Reserved
8
Reserved
[009] - [020]
For Future Use
[021] - [023]
Entrance and Exit Delays
Program Entrace Delay 1, Entrance Delay 2 and the Exit Delay in addresses [021] through [023]. Times are
programmed in seconds; valid entries are from 01 to 99 seconds.
[024] - [029]
System Times
Program a 2-digit time in each Address from [024] through [029]. For times that require a time of day, enter the
time in the 24-hour format.
Address
Description
[024]
Siren/Bell Duration (minutes)
[025]
Fire Zone Activation Delay (seconds)
[026]
Fire Zone Restore Delay (seconds)
[027]
Zone Transmission Delay (seconds)
[028]
Fire Zone Transmission Delay (seconds)
[029]
Auto-Arm Delay (×10 seconds; valid entries are in the range of 01 to 25)
[030] - [032]
For Future Use
Programming Mode 22