![Sur-Gard SG Security DV8OOO Instruction Manual Download Page 28](http://html1.mh-extra.com/html/sur-gard/sg-security-dv8ooo/sg-security-dv8ooo_instruction-manual_1406536028.webp)
24
[802]
No Restoral Reports for Troubles on Zones 1 - 7
Zone trouble restoral reports can be disabled for each individual zone. When this Address is entered, the Zone
Lights will indicate which zones will generate trouble restoral reports:
• if a Zone Light is ON, no trouble restoral report will be generated
• if a Zone Light is OFF, a trouble restoral report will be generated
To turn Zone Lights ON or OFF, press the number key for the desired zone.
[803]
No Restoral Reports for Miscellaneous Alarms 1
Restoral reports for the events described below can be disabled. When this Address is entered, the Zone Lights
will indicate which events will generate trouble restoral reports:
• if a Zone Light is ON, no restoral report will be generated
• if a Zone Light is OFF, a restoral report will be generated
Zone Light
Event
1
Auxiliary Alarm
2
Printer Failure
3
Fire Trouble
4
Auxiliary Power Fuse
5
Ground Fault
6
Siren Cut
7
For Future Use
8
Fire Alarm
To turn Zone Lights ON or OFF, press the number key for the desired zone.
[804]
No Restoral Reports for Miscellaneous Alarms 2
Restoral reports for the events described below can be disabled. When this Address is entered, the Zone Lights
will indicate which events will generate trouble restoral reports:
• if a Zone Light is ON, no restoral report will be generated
• if a Zone Light is OFF, a restoral report will be generated
Zone Light
Event
1
For Future Use
2
DVAC Failure
3
AC Failure
4
Low Battery
5
For Future Use
6
For Future Use
7
For Future Use
8
For Future Use
To turn Zone Lights ON or OFF, press the number key for the desired zone.
Programming Mode 20
firealarmresources.com