Sur-Gard SG Security DV8OOO Instruction Manual Download Page 1

INSTALLATION

MANUAL

DV8OOO

Software Version 1.0

firealarmresources.com

firealarmresources.com

Summary of Contents for SG Security DV8OOO

Page 1: ...INSTALLATION MANUAL DV8OOO Software Version 1 0 firealarmresources com firealarmresources com...

Page 2: ...VACS F1F2 List 3 or a DVACS F1F2 List 1 subset which is connected to a DVACS HUB 324 or DVACS HUB 308 card DVACS is a registered trade mark of Electro Arts Limited and covers a wide variety of product...

Page 3: ...115 Zone Definitions 19 Zone Definitions 19 116 228 For Future Use 20 229 269 Trouble Definitions 21 270 300 For Future Use 21 301 315 Alarm and Restoral Codes for Zones 1 to 8 and Trouble Zones 1 to...

Page 4: ...0 033 Printer Set up 31 034 For Future Use 31 035 037 Programmable Output Types 31 038 062 For Future Use 31 063 Language Selection for Printer 31 064 For Future Use 31 065 Maximum Alarm Reports per Z...

Page 5: ...up Assignment Operation All Zones programmable as 1 of 15 types 8 Zones 1 normally closed high zone 7 programmable end of line resistor normally closed or normally open zones 1 Fire Input Class A 3 De...

Page 6: ...from damaging the control panel it is still possible to cause temporary disruption to the operation of the microprocessor causing it to lose track of the program sequence The DV8000 is equipped with...

Page 7: ...an unswitched AC source and the F1 F2 subset modem connection Remove the printed circuit board mounting hardware and Keypad from the cardboard retainer inside the cabinet Before attaching the cabinet...

Page 8: ...ogrammable Output Terminals PGM OUT 1 and PGM OUT 2 The operation of the PGM OUT 1 Terminal is determined by the value programmed in Mode 22 Address 035 The operation of the PGM OUT 2 Terminal is dete...

Page 9: ...r the various loops described above Zone 8 Zones 1 through 7 R1 R2 500 maximum R5 R6 500 maximum R3 R4 500 maximum R7 500 maximum Bell Supervision using Zone 8 Zone 8 may be used to supervise a Grade...

Page 10: ...s a system trouble Trouble conditions are described in the Instruction Manual in Modes 02 and 09 After testing program the Exit Delay Entry Delay and Bell Siren Cut off times to the desired values Als...

Page 11: ...ation instructions It is recommended that additional smoke detectors beyond those required be installed for increased protection The added areas include basement bedrooms dining rooms furnace room uti...

Page 12: ...Switches 1 5 6 and 7 ON switches 2 3 4 and 8 OFF Citizen iDP3530 Citizen 200GX Citizen iDP560rsl Epson LX810 Requires Epson 8146 Serial Card Configuring the Printer Follow the manufacturer s instructi...

Page 13: ...Access Codes are stored in the panel s EEPROM memory and are retained even after complete AC and battery failure Installer s Programming Code A default Installer s Programming Code of 8000 is program...

Page 14: ...ach time a zone is opened or closed Mode 08 Zone Alarms Memory Display Mode 09 Trouble Alarms Memory Display Mode 10 Keypad Panic Alarms Memory Display Mode 11 Send user message Mode 12 Display last u...

Page 15: ...onnections as described in the Installation section of this manual Apply power to the panel and program the system as described in the Programming Section of this panel When programming is complete te...

Page 16: ...ess 004 Light 2 has been selected the default Installer s Code will not be restored by the method described above This feature is designed to prevent an unauthorised person from restoring the factory...

Page 17: ...ht OFF Addresses Some Addresses allow options and functions to be enabled or disabled by turning Zone Lights ON and OFF When an Address of this type is entered Zone Lights 1 to 8 will indicate which o...

Page 18: ...advance to the next Address by pressing the key Display Any Address Move to any Address by pressing Key The Memory light will flash when the Key is pressed enter the 3 digit number of the desired Addr...

Page 19: ...s disarmed 09 Follow Group A Ready Status When programmed as 09 the output will be on whenever Group A is disarmed and in the ready state the output will be off whenever Group A is armed or otherwise...

Page 20: ...whenever the bell is activated and will remain activated for 30 minutes or until a valid code is entered 26 Bell Siren Output for Group A When programmed as 26 the output will be activated when the BE...

Page 21: ...s not apply to the Bell output A command from the central station always has priority over the normal programmed function The only exception applies when Programmable Output 1 is programmed for use wi...

Page 22: ...s The control panel should be programmed to respond to one All Call command only Response to All Call 1 and All Call 2 should be evenly divided amongst all systems polled by the central station Two sy...

Page 23: ...trol panel is disarmed When a 24 Hour Audible zone is tripped it will be reported to the monitoring station and the event will be stored in memory Also the bell siren will sound and the alarm will be...

Page 24: ...same manner as a Delay 1 zone but may be assigned a different Entry Delay time The Entry Delay time for Delay 2 zones is programmed in Mode 22 Address 022 Zone Type B Probation This zone definition is...

Page 25: ...m 269 Invalid Code 270 300 For Future Use 301 315 Alarm and Restoral Codes for Zones 1 to 8 and Trouble Zones 1 to 7 Program a 2 digit Alarm Code at each address from 301 through 315 316 428 For Futur...

Page 26: ...tation the system transmits a code to the central station to have the desired message printed or displayed at the receiver The User Message Function Byte determines which printer message will be used...

Page 27: ...ication Rst Zn E0 for testing finished indication To change the Test Mode Function Byte enter a 2 digit hexadecimal code in this Address Refer to Appendix C 4 2 Format with Sur Gard Schedule 3A for a...

Page 28: ...generated if a Zone Light is OFF a restoral report will be generated Zone Light Event 1 Auxiliary Alarm 2 Printer Failure 3 Fire Trouble 4 Auxiliary Power Fuse 5 Ground Fault 6 Siren Cut 7 For Future...

Page 29: ...d will be used to indicate which Access Codes have been assigned to the group When a zone light is OFF that Access Code has not been assigned to the group When a zone light is ON that Access Code has...

Page 30: ...ne lights on the keypad will be used to indicate which zones are able to be bypassed When a zone light is OFF that zone may be bypassed When a zone light is ON that zone may not be bypassed For exampl...

Page 31: ...d on 3 Force Arming Select When on the system may be armed even when zones are open However all armed zones must be closed at the end of the Exit Delay or alarms will be generated 4 Reserved 5 Quick A...

Page 32: ...stem The keyswitch must be wired to the AUXIN and COM terminals Note that the end of line resistor must not be removed 6 Maintained Keyswitch Arming Disarming When on a normally open maintained keyswi...

Page 33: ...elay Instant zone Type 6 or E is left open and all of the Groups to which it is assigned are armed an alarm will be generated immediately Address 006 System Options Light 1 Reserved 2 Reserved 3 Reser...

Page 34: ...ses 301 through 308 When on bypass reports will be printed at the central station as BypZnXX where XX is the zone s alarm code When off the bypass reporting code for a zone is taken from the codes pro...

Page 35: ...ge English 02 2nd Language French 064 For Future Use 065 Maximum Alarm Reports per Zone per Armed Period The number of alarms a zone can generate within an armed period can be limited This feature is...

Page 36: ...program the value as 0 Zone 8 is a Normally Closed Zone and cannot be changed Trouble status for Zones 1 through 7 will only be active if these zones are programmed as End of Line Resistor Zones WARNI...

Page 37: ...ble Indication Option 0 No audible indication when a zone is tested 1 Siren will sound when a zone is tested 2 Keypad Sounder will sound when a zone is tested 3 Siren and Keypad Sounder will sound whe...

Page 38: ...em will return to the Arm Disarm mode NOTE If an alarm occurs during printing the system will cancel the Programming Mode printout if the alarm is programmed to be sent to the local printer Mode 29 In...

Page 39: ...tion Master Slave Options Enabled Lock out L K Yes Long Transmission L T delay at 4 seconds Yes Poll and Cut P C Yes Count and Cut C C set at 16 Yes F1 F2 Subset Options EIA L N and X Yes 10 mA T1 Yes...

Page 40: ...100 125 7D 0111 1101 126 7E 0111 1110 127 7F 0111 1111 DEC HEX BINARY 128 80 1000 0000 129 81 1000 0001 130 82 1000 0010 131 83 1000 0011 132 84 1000 0100 133 85 1000 0101 134 86 1000 0110 135 87 1000...

Page 41: ...ages 30 Installer Default Programming 99 Language Selection Programmable Output Types 01 Kiss off Signal 02 Fail to Communicate Line Cut 03 Courtesy Light 04 Follow Bell Siren 05 Follow Group A Armed...

Page 42: ...rming Disarming 7 Reserved 8 Reserved 004 1 Programmable Output 3 Normally High 2 Installer Lockout 3 Keypad Lockout 4 Reserved 5 Reserved 6 Reserved 7 Reserved 8 Immediate AC Failure Report Address O...

Page 43: ...Trb Rst Zn E8 EF E8 EF 6B F0 FF Do Not Use XXXXX represents variable messages refer to MLR1 Library The following are outputs for bypasses and clearing bypasses Printer Computer Zone Message Zone Byte...

Page 44: ...ne 7 108 7 Zone 8 109 C Trouble Zone 1 110 C Trouble Zone 2 111 C Trouble Zone 3 112 C Trouble Zone 4 113 C Trouble Zone 5 114 C Trouble Zone 6 115 C Trouble Zone 7 Zone Definitions 0 24 hour Silent 1...

Page 45: ...m 269 1 Invalid Code Trouble Definitions 0 24 hour Silent 1 24 hour Audible 2 24 hour Pulsed Bell 3 Day Loop 4 Day Loop and Buzzer 7 Instant 8 Buzzer Only 9 No Alarm B Probation C 10 second Buzzer wit...

Page 46: ...il to Arm on Schedule 2 442 D F Fail to Arm on Schedule 3 443 0 0 Reserved 444 9 2 Ground Fault 445 465 For Future Use Page 22 466 469 Keypad Alarm Reporting Codes Page 22 Address Default 466 E 8 Fire...

Page 47: ...23 801 804 No Restoral Report Page 23 Address Default 801 Light 1 OFF Zone 1 Light 2 OFF Zone 2 Light 3 OFF Zone 3 Light 4 OFF Zone 4 Light 5 OFF Zone 5 Light 6 OFF Zone 6 Light 7 OFF Zone 7 Light 8...

Page 48: ...Fault Light 6 OFF Siren Cut Light 7 OFF For Future Use Light 8 OFF Fire Alarm Address Default 804 Light 1 OFF For Future Use Light 2 OFF DVAC Line Failure Light 3 OFF AC Failure Light 4 OFF Low Batter...

Page 49: ...Page 25 Address Default 003 Light 1 OFF Zone 1 Light 2 OFF Zone 2 Light 3 OFF Zone 3 Light 4 OFF Zone 4 Light 5 OFF Zone 5 Light 6 OFF Zone 6 Light 7 OFF Zone 7 Light 8 OFF Zone 8 004 For Future Use...

Page 50: ...dress Default 010 Light 1 ON Code 9 Light 2 ON Code 10 Light 3 ON Code 11 Light 4 ON Code 12 Light 5 ON Code 13 Light 6 ON Code 14 Light 7 ON Code 15 Light 8 ON Code 16 011 016 For Future Use Page 25...

Page 51: ...Access Code Assignment Page 26 Address Default 033 Light 1 OFF Code 65 Schedule 1 Auto Arming Light 2 OFF Code 66 Schedule 2 Auto Arming Light 3 OFF Code 67 Schedule 3 Auto Arming Light 4 OFF Code 68...

Page 52: ...Light 5 OFF Code 69 Keyswitch Arming Light 6 OFF Code 70 Arming by Central Station Light 7 OFF Code 71 Reserved Light 8 OFF Code 72 Reserved 050 056 For Future Use Page 26 057 058 Group D Access Code...

Page 53: ...FF Zone 1 Light 2 OFF Zone 2 Light 3 OFF Zone 3 Light 4 OFF Zone 4 Light 5 OFF Zone 5 Light 6 OFF Zone 6 Light 7 OFF Zone 7 Light 8 OFF Zone 8 081 For Future Use Page 26 082 083 Zone Transmission Dela...

Page 54: ...OFF Option 14 Quick Exit Light 7 OFF Option 15 No arming on AC failure and low battery Light 8 OFF Option 16 Reserved Address Default 003 Light 1 OFF Option 17 Master Code not Changeable Light 2 ON Op...

Page 55: ...ion 48 Reserved Address Default 007 Light 1 OFF Option 49 Reserved Light 2 ON Option 50 Auto Clear Bypasses on Entry Light 3 OFF Option 51 All Closed Report Light 4 OFF Option 52 Opening Report on Ala...

Page 56: ...m Disarm Status 07 Follow Group C Arm Disarm Status 08 Follow Group D Arm Disarm Status 09 Follow Group A Ready Status 10 Follow Group B Ready Status 11 Follow Group C Ready Status 12 Follow Group D R...

Page 57: ...for Printer Page 31 Default 0 1 01 1st Language English 02 2nd Language French 064 For Future Use Page 31 065 Maximum Alarm Reports Per Zone Per Armed Period Page 31 Default 0 F firealarmresources co...

Page 58: ...ddress Default 051 0 Zone 1 052 0 Zone 2 053 0 Zone 3 054 0 Zone 4 055 0 Zone 5 056 0 Zone 6 057 0 Zone 7 058 400 For Future Use Page 32 401 408 Individual Bypass Reporting Codes Page 32 Address Defau...

Page 59: ...55 HOOK UP DIAGRAM firealarmresources com firealarmresources com...

Page 60: ..._______ _________________________ _______________________________ 3 _______ _________________________ _______________________________ 4 _______ _________________________ ______________________________...

Page 61: ...___ 7 _______ ________________________________ 8 _______ ________________________________ 9 _______ ________________________________ 10 _______ ________________________________ 11 _______ ____________...

Page 62: ...eu of any and all other warranties whether expressed or implied and of all other obligations or liabilities on the part of Sur Gard Ltd Sur Gard Ltd neither assumes nor authorizes any other person pur...

Page 63: ...cations 401 Magnetic Drive Units 24 28 Downsview Ontario Canada M3J 3H9 Tel 416 665 4494 Fax 416 665 4222 Toll Free 1 800 418 7618 www sur gard com 29001398 R002 Printed in Canada firealarmresources c...

Reviews: