Annex 2 - Victron Inverter connection
with Li.ONESS
Note
It is mandatory to use Victron’s CCGX device to
connect Sunlight’s Li.ONESS
Electrical connection
•
Connect the positive (+) cable from Power unit
(inverter) to Victron (+) DC terminal.
•
Connect the negative (-) cable from Power unit
(inverter) to Victron (-) DC terminal.
Note
DO NOT CONNECT INVERTER WITH ANY
OTHER EXTERNAL SOURCE (GRID, GENERATOR)
OR ANY OTHER LOAD (AC1 and AC2 IS NOT
CONNECTED ANYWHERE)
The following connections are necessary for
the correct operation of Sunlight’s battery
with Victron inverter (through CCGX device).
1. Connect the two cables (black and red) to the
battery’s terminal cables or inverter’s DC cable
(which come from the battery) in order to
power up the CCGX color control display.
Power in V+ Red Cable
8-70V DC GND Black cable
2. Connect the Ve.Bus from the CCGX device to
the Inverter’s communication port Ve.Bus 1 or
Ve.Bus 2 (both are the same) with a RJ-45 cable.
3. Connect the Ve.Can from CCGX device to the
communication port INVERTER COM of the
power unit with the modified RJ-45 cable.
•
VE.Bus connects to Inverter at inverter
•
VE.Can connects to Inverter Com at battery
•
Ethernet connects to router
•
Power in V+ Power CCGX from the positive (+)
battery terminal
•
8-70VDC GND Power CCGX from the negative (-)
battery terminal
Picture A2.1
DC Connection points
Picture A2.2
Power Unit & CCGX display
Picture A2.3
CCGX display back view