65
16.1.2 T
EMPORARY
F
AULTS
–
F
C
ODES
(A
UTOMATICALLY
R
ESET
)
Fault
Code
Fault Description
Possible Causes
Cure
Flue Sensor
Partially Blocked Exhaust Flue.
Check flue for partial blockages.
F7
Tripped on
Incorrect Combustion.
Check combustion on high/low fire.
High Temperature Flue Gas Sensor Fault.
Check the flue gas sensor.
Flow Sensor Damaged.
F10
Flow Sensor 1
Flow Sensor Wiring Damaged.
Check flow sensor & wiring, replace if faulty.
Fault
Flow Sensor Wiring Disconnected.
Return Sensor Damaged.
F11
Return Sensor
Return Sensor Wiring Damaged.
Check return sensor & wiring, replace if
faulty.
Fault
Return Sensor Wiring
Disconnected.
DHW Sensor Damaged.
F12
DHW Sensor
DHW Sensor Wiring Damaged.
Check DHW sensor & wiring, replace if faulty
Fault
DHW Sensor Wiring Disconnected.
Flue Sensor Damaged
F13
Flue Sensor
Flue Sensor Wiring Damaged
Check flue sensor & wiring, replace if faulty.
Fault
Flue Sensor Wiring Disconnected
Flue Sensor Damaged
F14
Flow Sensor 2
Flue Sensor Wiring Damaged
Check flue sensor & wiring, replace if faulty.
Fault
Flue Sensor Wiring Disconnected
No 230v Power Supply
Check the 3-pin plug on the fan.
F15
Fan Fault
No Tacho Signal
Check the 5-pin plug on the fan.
Fan Damaged
Replace fan.
Reset button on
Reset Button on Controller Fitted
on
Check the reset button and replace the
F26
Controller on Gas
Gas Valve is Blocked or Faulty
controller on the gas valve if necessary
Valve Fault
F34
Supply Voltage
Supply Voltage is Under 170 Volts
Check the mains supply voltage
Fault
F35
Supply Frequency
Supply Frequency is Incorrect and
not
Check the mains supply frequency
Fault
50Hz
F37
Water Pressure
Low System Water Pressure
Check water system pressure
Switch Open
F39
Outside
Sensor or Wiring Fault
Check wiring, replace outside sensor
Sensor Fault
No Outside Temperature Reading
Check boiler controller settings
Cascade
Sensor Damaged
F50
Temperature
Wiring Shorted
Check sensor & wiring, replace if faulty
Sensor Fault
Wiring Disconnected
F52
Heating Sensor
Heating Sensor Damaged
Replace the sensor
F66
Controller Fault
Controller Internal Error
Check earth connection, replace controller.
No Comm
F99
between
Controller
Wiring Disconnected
Check the wiring of the 6 wires between
and Display
controller and display