44
10.4.3 C
ONFIGURATION
P
ARAMETER
-
B
There is a total of 16 parameters within the configuration parameter.
Each parameter is listed in the below table along with what they are set to as standard.
Index Description
Range
S-FX 70
S-FX 125
S-FX 220
S-FX 320
b01
Type of Gas
0 = Natural Gas
1 = LPG
0
0
0
0
b02
S-FX Boiler Model 1 to 3 = Not Used
4 = S-FX 220 (Solo)
5 = S-FX 220 with dhw pump
6 = S-FX 220 with 3 way
valve & dhw storage pump
7 = S-FX 70,125 & 320 Solo
8 = S-FX 70,125 & 320 with
dhw pump
9 = S-FX 70,125 & 320 with 3
way valve & dhw pump
7
7
4
7
b03
Water Pressure
Protection
0 = Water Pressure Switch
1
– 5 = Not Used
0
0
0
0
b04
Max Fan Freq in
DHW mode
With b02 set to 4
With b02 set to 7
210 Hz
200 Hz
180 Hz
190 Hz
b05
Max Fan Freq in
CH mode
With b02 set to 4
With b02 set to 7
210 Hz
200 Hz
180 Hz
190 Hz
b06
Min Fan Freq in
CH/DHW mode
With b02 set to 4
With b02 set to 7
50 Hz
50 Hz
50 Hz
50 Hz
b07
Min Fan Freq
offset
With b02 set to 4
With b02 set to 7
40 Hz
40 Hz
40 Hz
40 Hz
b08
Function of
Variable Output
Relay
0 = Burner On
1 = Legionella Pump
2 = Boiler Room Ventilation
3 = Motor Drive O/O Valve
0
0
0
0
b09
Post Ventilation
0
– 120 Seconds
30
30
30
30
b10
Boiler Room Pre-
Ventilation
1
– 15 Minutes
1
1
1
1
b11
Boiler Room Post-
Ventilation
1
– 15 Minutes
1
1
1
1
b12
Flue Sensor
0 = Deactivated
1 = Enabled
1
1
1
1
b13
H/Ex 2 Protection
Not Used
-
-
-
-
b14
Max Flue Gas
Temperature
With b02 set to 4
With b02 set to 7
110c
110c
110c
110c
b15
Type of Fan
With b02 set to 4
With b02 set to 7
0
0
0
3
b16
Pump anti-locking
operating time
0
– 20 seconds
5
5
5
5