26
8.7 Other Flue Terminal Minimum Distances
All measurements are in mm
Terminal Location
Boiler Manufacturers & IGEM-UP-10 Boilers Rated >70kW
<333kW Net Input (Fan Draught)
A
Directly below an opening into the building
2500
B
Below gutter soil pipes etc.
200
C
Below Eaves
200
D
Below balconies or car port roof
Not Recommended **
E
From vertical drain or soil pipe etc.
150
F
From internal or external corners
If < 2500 - use plume kit & plume kit extensions
G
Above ground or balcony level
3000
H
From a surface facing the terminal
23.126 x (kW net input) + 618.84
I
From a terminal facing the terminal *
19.32 x (kW net input) + 647.59
J
From opening in a carport into a dwelling
Not Recommended **
K
Vertically from a terminal on the same wall
2500mm
L
Horizontally from a terminal on the same wall
Exhaust Only
– No Minimum Distance
M
Above an opening into the building
7.232 x (kW net input) + 93.708
N
Horizontally to an opening into the building
7.232 x (kW net input) + 93.708
P
Above a flat roof (Obstacle > 2500mm)
7.232 x (kW net input) + 93.708
P+ Above a flat roof (Obstacle < 2500mm)
4.5675 x (kW net input) + 19.723
Q
From an adjacent wall (Edge of terminal)
4.5675 x (kW net input) + 19.723
R
To an opening into the building
7.232 x (kW net input) + 93.708
S
From any other terminal
Exhaust Only
– No Minimum Distance
T
Above a >20 Deg Pitched Roof (BOT)
4.5675 x (kW net input) + 19.723
T+ Above a >20 Deg Pitched Roof (BOT) - Valley
4.5675 x (kW net input) + 19.723
*Positions not recommended **Risk assessment required (Chapter 9.11) BOT = Base of Terminal