64
10.11.4 D
ISPLAY
The following graphs describe how to programme the outdoor graph settings.
Operating screen:
H E A T I N G : b o i l e r
o f f
> > > : 1 2 3 . 4 ° C ( 1 2 3
. 4 ° C )
Press [MENU]
Select "Outdoor" using [◄] & [►] and press [ENTER]
Main menu screen:
M a i n M e n u
O u t d o o r
Press [◄] & [►] to browse through the screens that are shown below.
Press [▲] [▼] to change the blinking value in the selected screen.
Press [MENU] to exit. The unit will reset and go to the operating screen.
Press [ENTER] for confirmation screen after all changes are made.
Confirmation screen:
A r e
y o u
s u r e
<
C a n c e l ;
>
C o n f i r m
Press [
◄
] to cancel the changes made (unit will reset).
Press [
►
] to confirm the changes made. The time and day will
start blinking for a few seconds. After this, the display returns
to its operating screen.
0 1
O u t s i d P r e s
P5 AA
0
0 2
H C m i n O u T m p
P5 AC
- 1 5
° C
0 3
H C m i n F l T m p
P5 AD
8 5
° C
0 4
H C m a x O u T m p
P5 AE
2 0
° C
0 5
H C m a x F l T m p
P5 AF
2 0
° C
0 6
H C m i n F l L i m
P5 AG
2 0
° C
0 7
S u m S h D w n O u
P5 AH
3 0
° C
0 8
H C m a x F l L i m
P6 BA
8 5
° C
0 9
H C n g h t s h f
t
P6 BB
- 1 0
° C
0 A
H C p a r a s h f
t
P6 BC
5
° C
0 B
O u t S 1 2 k 1 0 k
P5 AR
0