76
Menu C: Cascade
C 4
E x t r a u n i t
0
Function for the cascading of the boiler(s).
This parameter is activated when an external (extra) boiler is
connected to the Master boiler. Connect to the Master con-
nections 21-22.
Menu C: Cascade
C 5
C a s
S i / M a
0
Function for the cascading of the boiler(s).
This parameter sets the function of the boiler at a cascade
alignment
0 = Single / Slave unit
1 = Master unit
Menu C: Cascade
C 6
P w r O f f T o C a
0
Function for the cascading of the boiler(s).
This parameter determines the function of the Slave boilers
when the Master boiler is switched off.
0 = Slave boiler(s) continue operation
1 = Slave boiler(s) switch off
Menu C: Cascade
C 7
C o m F l u N u m
0
Function for the cascading of the boiler(s).
This parameter determines the number of cascaded boilers,
that are implemented with a common flue system.
Menu D: General
D 1
0 - 1 0 V c o n t r
0
Function for the external control of the boiler by using a 0-10
Volt signal (Connections 15-16).
0 = No external control
1 = Control based on temperature setting
2 = Control based on power setting
Menu D: General
D 2
0 - 1 0 M i n T m p
2 0
° C
Function for the external control of the boiler by using a 0-10
Volt signal (Connections 15-16).
Control based on temperature (setting 1).
The minimum (desired) CH water temperature when
supplying a 1,4 Volt signal.
Menu D: General
D 3
A l t
*
1 0 0 f
0
Function for setting the location height (above sea level) of
the boiler.
NOTICE: dimensions in English feet. One unit = 100 ft.
Use this function only in consultation with the supplier/manu-
facturer.
The screen texts on these
pages are standard part of
the software and apply to
CH
systems
(boilers)
and/or DHW devices (wa-
ter heaters).