ETTING PARAMETER
P4BD
GAS TYPE
(
DISPLAY
D8)
In case of gas conversion, change parameter P4BD to the correct setting for both burners, for the top burner on the
left control panel and for the bottom burner on the right control panel:
•
start from screen showing: "no demand", "standby" or "burning"
•
press [ON/OFF] button for 2 seconds to switch to programming mode: "heating: boiler off"
•
press [MENU] for 3 seconds: "Main menu - Clock"
•
press
◄ button to select "Main menu - parameter", press [ENTER]
•
enter password level 2: press
◄► to select the number, press ▲▼to adjust, press [ENTER]
•
after confirmation, the display shows "A1 Step modul"
•
press
◄ button to select "D8 Gas type"
•
press
▲▼to select the correct setting: 0 = standard gas; e.g.: natural gas (G20/G25.3)
1 = propane (G31)
2 = B/P (G30/G31)
•
press [ENTER] to confirm, boiler returns to programming mode "heating: boiler off".
•
press [ON/OFF] button for 3 seconds to switch to base screen "no demand", "standby" or "burning"
Repeat this procedure on the other panel for the other burner.