10.11.3 O
UTDOOR GRAPH
-
ADDITIONAL SETTINGS
Curve and values only for illustration purposes, programmed parameter values can deviate!
P5 AG
Heat curve minimum flow temperature
°C
The set point will never be lower than the flow temperature set in parameter P5 AG. The minimum temperature is
limited, even if the calculated set temperature, according to the heating curve, would be lower.
P5 AH
Summer outside temperature central heating
°C
If the outside temperature is higher than set in P5AH the heat demand for heating will be blocked.
P5AR
Outdoor sensor 10K or 12K resistance (1 or 0)
Dep
ending to the used type of sensor this parameter can be set. Set to ‘0’ when using a so called 12k NTC sensor
(sensor resistance is 12 kohm at 25°C) Set to ‘1’ when using a so called 10k NTC sensor (sensor resistance is 10
kohm at 25°C) Default the paramet
er = 0, so the used sensor is assumed to be 12 kΩ.
P2 HA
Outdoor sensor hysteresis
°C
If
the outdoor temperature reaches the temperature set in P5 AH (Warm weather shutdown) the unit won’t start for
heating. If the measured outdoor temperature drops P5 AH minus P2 HA the boiler can start up for heating again.
P6 BA
CH User Setting
°C
The set point will never be higher than the flow temperature set in parameter P6BA. The maximum temperature is
limited, even if the calculated set temperature, according to the heating curve, would be higher.
P6 BB
Heat curve night shift
°C
The temperature reduction during the night, relative to the setting determined by the heat curve
FLO
W
T
E
M
P
E
R
A
TU
R
E
OUTSIDE TEMPERATURE
P5 AG
- min flow temp
P5 AH
- Warm weather shutdown
P2 HA
- Outdoor sensor hysteresis
HEATING CURVE
- additional settings
P6 BB
- Heatcurve night shift
P6 BA
- max flow temp
10
20
40
50
60
70
80
90
0
30
-10
0
-20
-30
-40
10
20
30
40