62
10.11.2 O
UTDOOR GRAPH
-
MAIN SETTINGS
Curve and values only for illustration purposes, programmed parameter values can deviate!
P5 AC
Heat curve minimum outside temperature
°C
This sets the minimum outside temperature at which one wants the maximum flow temperature that is set.
P5 AD
Heat curve flow temperature at minimum
°C
This sets the desired maximum flow temperature at the set minimum outside temperature.
P5 AE
Heat curve maximum outside temperature
°C
This sets the maximum outside temperature at which one wants the minimum flow temperature that is set.
P5 AF
Heat curve flow temperature at maximum
°C
This sets the desired minimum flow temperature at the set maximum outside temperature.
P6 BC
Heat curve parallel shift
°C
The heating curve is set by the parameters. Next to these settings, set by the installer, the end user has the freedom
to influence the flow temperature by doing a parallel shift setting. In this parameter, the margins are set within which
the user can increase and decrease the calculated flow temperature relative to the calculated flow temperature by
the heating curve that was set.
OUTSIDE TEMPERATURE
FLO
W
T
E
M
P
E
R
A
TU
R
E
40
30
20
10
-40
-30
-20
0
-10
30
0
90
80
70
60
50
40
20
10
P5 AE
outside temp high
P5 AC
outside temp low
P5 AF
- Flow temp at
outside temp high
P5 AD
- Flow temp at outside temp low
P6 BC
- Parallel shift
HEATING CURVE
- main settings