27
C63
Closed
Air supply from
outside
* Appliance sold without flue/air-inlet ducts.
* The flue gas parts are not part of the boiler. The
boiler is intended to be connected to a separately
approved and marketed system for the supply of
combustion air and discharge of combustion
products.
Condensate is allowed to go to the boiler.
* Air supply inlet and flue gas outlet not at oppo-
site walls
* Technical data:
nominal T
flue gas
85°C
nominal Q
fluegas
see 2.2
1)
maximum T
fluegas
95°C
min. load T
fluegas
35°C
min. load Q
fluegas
see 2.2
1)
nominal % CO
2
see 2.2
1)
max. allowed draft
70Pa
max. pressure drop in-
let-outlet
200Pa
max T
air supply
40°C
max recirculation
10%
1) table technical specifications
Use the conditions of chapter 8.4 to select the
right parts.
8.4
C63 certified
In general, boilers are certified with their own flue gas material. For type
B23(P), C13, C33, C43, C53 and C83
systems, only use flue gas and air supply parts approved according chapter 4.2.
If a heater is C63 certified, no specific type flue gas material has been certified in combination with the boiler. In this
case the flue gas and air supply parts should comply with the applicable European standards (EN14989).
So, for type C63 systems flue gas and air supply parts from other suppliers can be used. It must be able to handle
the condensate forming (W) and transport, overpressure (P1) and must have a minimum temperature class of
T120
. Also, it has to meet the requirements in the following chapters "air supply" and "flue terminal".
CE string
flue gas
material
E
u
ro
p
e
a
n
s
ta
n
d
a
rd
Temp
e
ra
tu
re
c
las
s
P
re
s
s
u
re
c
las
s
R
e
s
is
ta
n
c
e
t
o
c
o
n
d
e
n
s
a
te
C
o
rr
o
s
ion
re-
s
is
ta
n
c
e
c
las
s
Met
a
l:
li
n
e
r
s
p
e
c
if
ic
a
tion
s
S
o
o
t
fire
r
e
s
is
-
ta
n
c
e
c
la
s
s
D
is
ta
n
c
e
t
o
c
o
mbu
s
tible
ma-
te
rial
P
la
s
ti
c
s
:
loc
a
tion
P
las
ti
c
s
:
fire
b
e
-
h
a
v
iou
r
P
la
s
ti
c
s
:
e
n
c
los
u
re
min. req. PP
EN 14471
T120 P1
W
1
O
30
I of E
C/E
L
min. req. SS
EN 1856-1 T120 P1
W
1
L20040
O
40
A few examples of flue gas material suitable for the S-CB
+
boilers:
-
CE String for Plastic PPs: EN14471 T120 P1 W 2 O(30) I C/E L
-
CE String for Stainless Steel: EN1856-1 T250 P1 W V2-L50040 O (50)
When selecting flue gas systems, be aware that the minimum requirements are met. So only select flue gas materials
having the same or better properties than this table.
Never use aluminium containing flue gas pipes in these boilers.
Connecting diameters and tolerances:
mat
d
nom
D
outside
L
insert
d
inside
L
insert
d
wall thickness
RVS
180
180 ± 0,3
50 ± 1
181,2 ± 0,3
50 +0/ -2
0,6 ± 10%
RVS
200
200 ± 0,3
50 ± 1
201,2 ± 0,3
50 +0/ -2
0,6 ± 10%
PP
200
200 +1/ -0,6
50 +20/ -2
202 +0,6/ -1 50 +20/ -2
≥ 3,5
Flue outlet