Page 38 of 54
LOGIC FUNCTION TABLE
No
Function
Description
Activation by
0
Deactivated
None
None
1
TARE
*
Adds the current display value to the tare
memory and sets the display to zero.
Falling edge
2
RESET TARE
*
Adds the tare memory to the display value
and clears the tare memory.
Falling edge
3
PEAK
Displays the peak value. (MAX.)
Low level
4
VALLEY
Displays the valley value. (MIN)
Low level
5
RESET
PEAK/VALLEY
Perform a reset of the peak or the valley,
depending on which is being displayed.
Falling edge
6
HOLD
Freeze the display while all the outputs
remain active
Low level
11
BRIGHTNESS
Change the display brightness from Hi to
Low
Low level
12
SETPOINT
VALUE
Displays the selected setpoint value (see
diagram next page)
Low level
13
False
Setpoints
Simulates that the instrument has a four
setpoints option installed
Low level
*
Only with mode TARE 1 and TARE 3
5.2.3 – Programming the logic functions
When the menu of logic functions has been accessed, by pressing
the
key, a logic function between 0 and 15 can be selected.
(As shown above)
If the selected function is number 12 and any of the Relay or NPN /
PNP options are installed, it will allow access to either of the two or
four setpoints available depending on the option, which will be the
value displayed by the instrument when this function is activated.