3.4 – Programming of Thermocouple input
When configuring the meter for thermocouple input, the
temperature ranges and resolution available are:
Input
Range (res. 0.1 º)
Range (res. 1º)
(-50.0 to +850.0) ºC
(-50 to +850) ºC
Thermo-couple J
(58.0 to +156.0) ºF
(58 to +156) ºF
(-50.0 to +1250.0) ºC
(-50 to +1250) ºC
Thermo-couple K
(-58.0 to +2282.0) ºF
(-58 to +2282) ºF
(-200.0 to +400.0) ºC
(-200 to +400) ºC
Thermo-couple T
(-328.0 to +752.0) ºF
(-328 to +752) ºF
The Thermocouple software menu allows selection of temperature
units (Celsius or Fahrenheit), resolution (degree or tenth of
degrees) and a display offset. Provision is made to allow for a
sensor offset. If there is a difference between the temperature
under measurement and the temperature read by the sensor, this
can be corrected by programming an offset from -9.9 to +9.9, with
0.1 º resolution, or from -99 to +99, with 1 º resolution.
LED
‘TARE’ will light up each time that an offset value is
programmed.