Page 23 of 54
Example:
In a process of temperature control the thermocouple
sensor is located in a part of the process where
temperature is 5 degrees below than the point at which the
control has to be done. By programming an offset of 5
points, with 1 degree resolution, the deviation will be
corrected.
Configurable parameters for this input are:
1.
Thermocouple type [J, K, T].
2.
Reading units in degree Celsius "º C" or Fahrenheit "ºF".
3.
Resolution in tenth of degrees "0.1º" or in whole degrees "1
º".
4.
Offset. Offset value is programmable up to ±9.9 º with tenths
resolution, or up to ±99 º with degree resolution. The
instrument comes from the factory with an offset=0
After introducing these parameters, the display range and
linearization for the selected thermocouple input are adjusted
automatically
.