Page 28 of 54
4.1.1 Programming of the scale
There are two methods for programming the scale, the
SCAL
method and the
tEACH
method. In the following diagram the SCAL
menu is shown as an example; it is exactly the same menu as the
tEACH menu.
SCAL method
Level 2
The Process Value and display values are programmed manually.
This method can be used when the value of the signal supplied by
the transducer at each points of the process is known. For example
input 1 = 4 display 1 =0: input 2 = 20 display 2 = 100. In process
mode, with mA range selected, this will display (0 to 100) for a (4
to 20) mA input signal.
3s
InP 3
±88.888
dSP 3
±188.88
3s
InP 2
±88.888
dSP 2
±188.88
2
CndSP
SCAL
InP 1
±88.888
dSP 1
±18888
±188.88
dec.point
Points =2
Points =3
3s
InP n
±88.888
dSP n
±188.88
Points =n
3s
InP 11
±88.888
dSP 11
±188.88
Points =11