Page 29 of 54
tEACH method
Level 2
The input values are introduced directly from the signal present on
the input connector when each point is programmed. The display
values are programmed manually. This method can be used when it
is possible to bring the process to the conditions of each one of the
points to be programmed.
Programming of the linearization points
Access the first two input-display co-ordinates by pressing on the
key. To access the rest of the points, press on
key for
approximately 3 s from the display value of point 2. This will allow
access to linearization points 3 to 11. After each process and
display value has been added press
key. This allows the next
point to be programmed. When all points have been programmed
(to a max of 11), press
for 3 s to exit linearization. Any points
(up to 11) that have not been programmed are omitted from the
display calculation.
InP 1 to 11
Level 3
Input points
−19999
to
99999
dSP 1 to 11
Level 3
Display points
−19999
to
19999
88.888
Level 3
Display decimal point
0
0
.
0
0
.
00
0
.
000
0
.
0000
Accessible from the SCAL or tEACH menu, following the first display
point. Once accessed, it will start to blink in its present position and
through the
key will be able to shift to another position.
Please note: moving the decimal point will also affect the setpoint
value and the value of the analog output scale, if output option has
been fitted.