Flashing
Red
Flashing
Green
G file configuration
doesn't match current
network setup. More than
one configured slave on
the network is inactive.
Make sure the network
is properly configured
in the G file and the
slaves are properly
attached to the
network.
71h
Saved configuration in
EEPROM doesn’t match
network setup.
Using the config port
on the scanner, verify
and save the network
configuration.
72h
Flashing
Red
Flashing
Red
If you try to put the SLC
into RUN mode while
configuring the network
devices, the LEDs will
continue to blink
alternately and the SLC
will fault with this fault
code.
Finish configuring the
network devices and
exit the configuration
utility.
73h
Any
Flashing
Red
AS-Interface power is too
low (less than 14.5V).
Make sure cable is
properly connected to
the scanner and make
sure the power supply
is properly connected
to the network. See
section 9.2.
61h
AS-Interface is in
configuration mode rather
than protected mode
Slave 0 is present and
Auto Address
Programming is
disabled. Configure the
slave address in the G
file.
74h
Slave at address 0
detected.
While in protected
mode, no slave may
occupy address 0.
Remove the delinquent
slave.
76h
AS-Interface is off-line.
75h
FAULT
LED
COMM
LEDs
Description Troubleshooting
SLC
Fault
Code
Summary of Contents for SST-ASI-SLC
Page 6: ...SST ASI SLC User s Guide vi Conformance Statement 63 CE Notice 67 C D...
Page 13: ...7 This chapter contains a system overview information on hardware features 2 Overview...
Page 20: ...SST ASI SLC User s Guide 14...
Page 30: ...SST ASI SLC User s Guide 24 IOM Ladder Logic Instruction...
Page 44: ...SST ASI SLC User s Guide 38...
Page 66: ...SST ASI SLC User s Guide 60...
Page 72: ...SST ASI SLC User s Guide 66...
Page 74: ...SST ASI SLC User s Guide 68...