SST-ASI-SLC User’s Guide
36
9. Save the configuration and perform a list command.
Config :> save
Saving....
EEPROM write was successful.
Config :> list
Slave ID IO P PID PIO
01 0 0 F 0 0
03 0 8 F 0 8
The PID and PIO values are now saved in EEPROM so they appear
in the display. If a slave has PID and PIO values displayed without
corresponding ID and I/O values, that slave has failed or is missing.
10. When you are finished, type
Exit
. You will be prompted to save
any changes. Changes will be saved to the EEPROM on the module.
Config :> exit
SAVE changes before exiting? (Y or N) y
Saving...
EEPROM write was successful.
Summary of Contents for SST-ASI-SLC