SST-ASI-SLC User’s Guide
50
3. The FAULT and COMM 1 LEDs flash red alternately to tell you the
scanner is in boot utility mode. The commands available are:
Ver
- display the current firmware version number
Help
- display available commands
LoadFlash
- load new firmware into flash
Run
- exit System Configuration mode
4. Type
LoadFlash
. The scanner responds with a query. Press
Y
to
start.
5. Initiate an Xmodem send of the module firmware file using your
communication software.
6. When the upload is complete, the scanner asks if you want to
program the new module into flash. Press
Y
to confirm.
7. When the module has been programmed into flash, use the
Ver
command to confirm that the version number is correct.
8. Cycle power on the SLC. If you don’t cycle power you may get
unpredictable results.