2.3 Button
The button is located at the top of the product and used to update the firmware.
Action
Description
Hold then power on
Bootload state to update firmware.
2.4 Configuration Switch
The configuration switches are located at the top of the product, Bit 1 is the function bit and Bit 2 is the mode bit.
Function
(Bit 1)
Mode
(Bit 2)
Mode
Description
Off
Off
Run mode
Allows configuration and communication.
On
Off
Debug mode
Allows configuration, communication and
debugging.
Off
On
Configuration mode
IP address is fixed at 192.168.0.11. Allows
configuration. Prohibits communication.
On
On
Run mode
Allows communication. Prohibits
configuration and debugging.
Note:
To apply mode switching, please restart the gateway.
2.5 Internal Series Resistor Switch
The GT200-HT-EI has an internal series resistor (270 Ohm /2 W) required for the HART channel, this allows up
to 13 HART instruments to be connected. When the power of the series resistor is more than 2W, you must use an
external series resistor (250 Ohm /3 W), allowing the gateway to be connected to up to 15 HART instruments.
Switch to ON, using the internal series resistor
Switch to OFF, using the external series resistor
Off
On 1 2