As is shown in the table, upper table shows the memory distribution of the HART input data, the lower table
shows the output data. When you need to change the output data, click the “stop” button first, then change the
related data or load the already saved data table. Then click the “sending data”.
5.2.8 Diagnose
Through this function, users will know which device is not communicating. The execution condition of
configured commands, data transmission of the gateway and the displays of certain command’s operating steps
are as follows:
1. Ensure that the GT200-HT-EI’s function bit of configuration switch is in the ON state and the mode bit of
configuration switch is in the OFF state, restart the gateway. GT200-HT-EI is in the debug mode.
Use a network line to connect the GT200-HT-EI’s RJ-45 port and a computer , Open the software “SST-HI-CFG”,
click “Tool—Diagnose” or click on the icon
, the software first pop up one dialog box to choose the
gateway and click “OK”.
2. Enter the interface of diagnose