User Manual
HART/EtherNet/IP Gateway
GT200-HT-EI
WWW.SSTAUTOMATION.COM
20
Note: The same command can only be configured once in one node.
※HART Common Commands
Note: The front two bytes of the actual response data is the status info of the device. The data after that two bytes is the
device response data.
Command 1 (Command ID1): Read Primary Variable
Return primary variable value in float data type.
Request: None
Response:
Byte
Description
Byte 0
Primary Variable Units
Byte 1-4
Primary Variable
Please check the picture of the SST configuration software below: