5.2.2.7 Advanced Options to Configure HART Commands
When using the HART command configuration, sometimes users want to get only one part of the data from one
command. For example, for No.1 HART command. The float value of the main variable is only needed, so there
is no need to get the units of the main variable, therefore the advanced option should be used. The advanced
options is the execution of the “segment mapping function”. It cuts the response data of the HART command and
isolates a segment of the data. Users can get any part of the data they want.
Below is the interface of the Advanced Options:
The below is the example of the No.3 HART command, this will demonstrate how to use the “Segment Mapping”
function. We can see the “configuration” button next to the “receive data project configuration” once the
configuration mode is set to “Advanced”, click it:
There are many parts in the “response data”. For example, “Command Status” means the communication status
and relevant code of the HART response command, “Byte0-3” means byte 0 to 3 of the data area of the HART