background image

HART / EtherNet/IP Gateway

GT200-HT-EI

User Manual

V 1.3

Rev B

SST Automation

Email: [email protected]

[email protected]

WWW.SSTAUTOMATION.COM

WWW.SSTCOMM.COM

Summary of Contents for GT200-HT-EI

Page 1: ...HART EtherNet IP Gateway GT200 HT EI User Manual V 1 3 Rev B SST Automation Email SUPPORT SSTAUTOMATION COM SUPPORT SSTCOMM COM WWW SSTAUTOMATION COM WWW SSTCOMM COM...

Page 2: ...out notifying users The product has many applications The users must make sure that all operations and results are in accordance with the safety of relevant fields and the safety includes laws rules c...

Page 3: ...Interface 5 2 7 Topology of GT200 HT EI and HART Instruments 6 3 Hardware Installation 8 3 1 Machine Dimension 8 3 2 Installation Method 8 4 Quick Start Guide 9 4 1 Connection 9 4 2 Configuration 9 4...

Page 4: ...ON COM 6 1 Data Exchange 37 6 2 Flowchart of Executing One HART Command 38 7 EtherNet IP Connection Parameters 39 8 How to Read Write I O Data 40 8 1 Read Write Data by IO Messaging Recommend 40 8 2 R...

Page 5: ...ART slave address and modification single point mode of coexistence of HART communication and 4 20mA data acquisition HART side supports the primary master and the secondary master Multi debugging fun...

Page 6: ...VDC 11V 30V 70mA 24VDC 15 Operating temperature 40 F 140 F 40 C 60 C Humidity 5 95 without condensation 16 Dimensions W H D 1 0 in 4 0 in 3 6 in 25 mm 100 mm 90 mm 17 Installation 35mm DIN RAIL 18 Pro...

Page 7: ...scription ENS Red off IP address initialization is normal Red blinking DHCP SNS Green on EtherNet IP connection is established Communication is normal Green blinking EtherNet IP connection is not esta...

Page 8: ...nication and debugging Off On Configuration mode IP address is fixed at 192 168 0 11 Allows configuration Prohibits communication On On Run mode Allows communication Prohibits configuration and debugg...

Page 9: ...2 6 3 HART Interface 1 2 3 HART LOOP HART LOOP NC Pin Description 1 Power GND 2 NC Not Connected 3 24V DC Pin Description S1 TXD Transmit Data Output S2 TXD Transmit Data Output S3 RXD Receive Data I...

Page 10: ...supply for the HART instruments and the GT200 HT EI to ensure stable communication 2 To improve the communication efficiency of the field bus it is recommended not to configure the empty node in SST...

Page 11: ...User Manual HART EtherNet IP Gateway GT200 HT EI WWW SSTAUTOMATION COM 7...

Page 12: ...HART EtherNet IP Gateway GT200 HT EI WWW SSTAUTOMATION COM 8 3 Hardware Installation 3 1 Machine Dimension Size width height depth 1 6 in 5 0 in 4 4 in 40mm 125mm 110mm 3 2 Installation Method Using 3...

Page 13: ...2 7 4 Power on the gateway and run the SST HI CFG software to start the configuration process 4 2 Configuration The following steps give an example configuration process but tailor your configuration...

Page 14: ...default configuration created by SST Automation You can change the parameters based on the default configuration or create a new project The following steps introduce how to configure for a new proje...

Page 15: ...has no request with 24 byte response and the command 06 has 2 byte request with 2 byte response The request data of the GT200 HT EI includes an extra 2 byte status so the receiving data length is 2 b...

Page 16: ...oad the configuration Click Download on the toolbar select the gateway you want to download to and click Sign In Note The GT200 HT EI will apply the new configuration after gateway restart After downl...

Page 17: ...ebug and monitor tools chapter5 2 7 5 2 8 5 2 9 For more EtherNet IP connection details refer to chapter 7 and chapter 8 1 Set the configuration switch to Bit 1 ON and Bit 2 OFF debug mode Restart the...

Page 18: ...click Memory on the toolbar and sign in the GT200 HT EI Check the data bytes and mapping address The input data in the Memory data window corresponds to the input at EtherNet IP side The output data...

Page 19: ...to configure the product GT200 HT EI You may also check the software user manual to get detailed usage Run the software and enter the main interface of software Tool Bar Toolbar interface shown as fol...

Page 20: ...oad Read the configuration information from the module and show in the software Download Download the configuration file to the gateway AutoMap Used to automatically calculate the mapped memory addres...

Page 21: ...es and relevant slave addresses the HART master is connecting with This also supports changing slave addresses 5 2 Software Function Description 5 2 1 Configure the Ethernet In the device view interfa...

Page 22: ...under the single point the gateway can only communicate with the slave device whose address is 0 Retries Select the number of retransmission commands ranging from 0 to 5 Polling Determines if the pol...

Page 23: ...l can only be equipped with one slave node which address is 0 when configured in the single point mode Note When configured node numbers are more than the actual connected devices the redundant node w...

Page 24: ...ytes of the actual response data is the status info of the device The data after that two bytes is the device response data Command 1 Command ID1 Read Primary Variable Return primary variable value in...

Page 25: ...primary variable current always matches the AO output current of the device A second third and fourth variable is defined for each device type E g The second variable is the sensor temperature etc Req...

Page 26: ...es not need to map all the variables to the Modbus TCP registers Please follow the guide below to switch to the Advanced Configuration Mode then click the Configuration button Only select the variable...

Page 27: ...e Basic and Advanced optional Basic is shown as above For the Advanced configuration please refer to chapter 4 2 3 7 Mode of outputting command You choose the execution way of the command change of st...

Page 28: ...is command The response data only includes data area of the HART frame The register starting address of receiving data The property is automatically calculated by the gateway used for register address...

Page 29: ...ion of the segment mapping function It cuts the response data of the HART command and isolates a segment of the data Users can get any part of the data they want Below is the interface of the Advanced...

Page 30: ...address which this byte is located in the memory buffer area of the GT200 HT EI EtherNet IP register address The relevant EtherNet IP register address of the Memory Address Note This address is not a...

Page 31: ...commands or more the memory unit will display a red color When the distributed memory exceeds the defined scale of gateway the exceeding part will display a yellow color The white color area represen...

Page 32: ...COM 28 5 2 5 Upload Configuration Open the software SST HI CFG Click on the upload icon Select the gateway you used in the pop up dialog box and click OK then upload data if it shows upload successfu...

Page 33: ...absence of the EtherNet IP side Steps are as follows 1 Ensure that the GT200 HT EI s function bit of configuration switch is in the ON state and the mode bit of configuration switch is in the OFF sta...

Page 34: ...e is not communicating The execution condition of configured commands data transmission of the gateway and the displays of certain command s operating steps are as follows 1 Ensure that the GT200 HT E...

Page 35: ...ick on the HartChannel0 in this interface it will show the status of the HART fieldbus part on the right Press the Refresh button this will update the data once Click on Periodically refresh to have t...

Page 36: ...is will refresh these command status Periodically refresh will refresh the command status once 4 Double clicking the commands will show their command information command 03 can start data input Click...

Page 37: ...ation switch is in the ON state and the mode bit of configuration switch is in the OFF state restart the gateway Now GT200 HT EI is in the debug mode 2 Use a network line to connect the GT200 HT EI s...

Page 38: ...modify the slave address The operation steps are 1 Dial the configuration switch of GT200 HT EI to 1ON 2OF which will set the gateway into debug mode 2 Use a network line to connect GT200 HT EI to a...

Page 39: ...nterface it will show the short address long address and ID of HART slave devices which are connected to the gateway Move to the relevant device and right click it and click Modify slave address will...

Page 40: ...SSTAUTOMATION COM 36 After modification the HART slave address has been modified the gateway must be restarted 5 2 11 Conversion Tools In the Tools menu there are two practical tools They are used to...

Page 41: ...t buffer The received data from the HART instruments will be mapped to the input buffer for the EtherNet IP scanner reading The output data from EtherNet IP scanner will be mapped to the output buffer...

Page 42: ...User Manual HART EtherNet IP Gateway GT200 HT EI WWW SSTAUTOMATION COM 38 6 2 Flowchart of Executing One HART Command...

Page 43: ...are as below Parameters Data Size 64 Bytes 128 Bytes 256 Bytes Input Instance 102 112 122 Output Instance 101 111 121 Configuration Instance 103 113 123 Notes The Input data size should include a 4 b...

Page 44: ...ta The following RSLogix 5000 example will describe how to read write I O data 8 1 Read Write Data by IO Messaging Recommend Right click on EtherNet IP scanner module click New Module as shown below I...

Page 45: ...shown below In the above picture the module information needs to be configured includes Name Name the added EtherNet IP adapter module Comm Format Configure data types Users can choose data types as D...

Page 46: ...he software SST HI CFG Connection Parameters Set Connection parameters during communication Please refer to chapter 7 Note Size configured bytes in the above picture should be consistent with the rele...

Page 47: ...O Data 0 SSTGateway O Data 31 is the corresponding output data address of the SST Gateway module in scanner Unfold SSTGateway I as shown below In the above picture the first 4 bytes of SSTGateway I Da...

Page 48: ...4 8 2 Read Write Data by MSG 8 2 1 Read Data Create a new project Ensure it is in the Offline mode Add two new tags ReadTag and ReadData under the Controller Tags and set the type of ReadTag as MESSAG...

Page 49: ...e Select Get Attribute Single now relevant service code will become e Hex Class 4 Hex Instance Please refer to chapter 7 EtherNet IP Connection Parameters Set Attribute 3 Hex Destination Select ReadDa...

Page 50: ...dapter after setting the path click Apply Confirm As is shown below In this instance EtherNet IP hostname is Scanner EtherNet IP scanner slot No Is 2 EtherNet IP adapter is 192 168 0 10 IP address of...

Page 51: ...d some logic commands to trigger this command in the common program For more detailed information please refer to RSLogix5000 Download the program to the PLC and set PLC into the Online state Click Co...

Page 52: ...Net IP Gateway GT200 HT EI WWW SSTAUTOMATION COM 48 8 2 2 Write Data Enter the Offline mode add two new tags WriteTag and WriteData under the Controller Tags Define the type of WriteTag as MESSAGE and...

Page 53: ...y GT200 HT EI WWW SSTAUTOMATION COM 49 Enter the Monitor Tags interface input some data beginning from address WriteData 0 in the WriteData tag There data will be outputted to SST Gateway Right click...

Page 54: ...t Attribute Single now relevant Service Code will become 10 Hex Class 4 Hex Instance Please refer to chapter 7 EtherNet IP Connection Parameters Set Attribute 3 Hex Source Element Select WriteData tag...

Page 55: ...herNet IP scanner slot No IP address of EtherNet IP adapter after setting the path click Apply Confirm As is shown below In this instance EtherNet IP hostname is Scanner EtherNet IP scanner slot No Is...

Page 56: ...T EI WWW SSTAUTOMATION COM 52 Control as shown below Download the PLC program to the PLC and set PLC to the Online state the data in the WriteData will be outputted to EtherNet IP adapter SST Gateway...