7 .5 Resetting of all addresses in a network
Reset via hardware bridge
Note:
If this action is carried out, all CAN bus addresses of each participant are
irreversibly deleted.
The following steps must be followed:
1.
Switch off the power supply of the HOLDX process lock
2.
Make an electrical connection between Pin 5 (X1) and Pin 7 (X1) on the HOLDX
master (short circuit)
3.
Switch on the power supply again and keep it switched on for at least 10 s
4.
After successful reset, all three LEDs (red, green, blue) of all HOLDX process locks must
flash continuously (see also flashing codes - Table 1+ 2)
5.
Switch off the power supply of the HOLDX process lock
6.
Remove again the electrical connection between Pin 5 (X1) and Pin 7 (X1).