SplashMe Automation Controller 1.0 | Installation and Operating Instructions
© Nymet Innovations Pty Ltd 2019 | Revised November 2019
45
5.2.4 – Auxiliary connections (actuator valves, equipment, 15A-3phase)
Actuator valves
The SplashMe Automation Controller has 4 x volt-free terminal blocks suitable to control
actuator valves. These outputs are AUX5, AUX6, AUX7, AUX8.
Note the connection outlet number so it can be correctly assigned when setting up the
SplashMe App.
Instructions
Obtain a power supply of the correct voltage and current needed to run the actuators
installed with the system.
1.
Install actuator valve as per manufactures specification
2.
Remove the front cover of the SplashMe Automation Controller (section 5.2.2)
3.
Run the actuator and power supply wires through the bottom cable grommet
4.
Group the negative wires from each of the actuators to be operated together join
with the negative wire of the power supply
5.
Group all the NO wires of the actuators to be operated together and connect to the
NO terminal of selected AUX contact
6.
Group all the NC wires of the actuators to be operated together and connect to the
NC terminal of selected AUX contact
7.
Connect the positive wire of the power supply to the C terminal of the selected
AUX contact
Warning
All electrical connections and installations to be done by a
licenced
electrician
AUX 5-8 is for the connection of Safety Isolated (SELV) Supply /
Loads only