IM-P707-01
CTLS Issue 1
68
SP8-10 Smart positioner
5.1.27 Menu: Analogue feedback
Menu/parameter
Value range
Description
Analogue Out Min.
4.0 to 18.4 mA
Use this parameter to specify the lower current range
limit for the Analogue feedback. The current range
corresponds to the configured stroke range.
Note:
The current range limits can be freely configured
between 4 and 18.5 mA. However, the current range
must not be smaller than 10 % (1.6 mA).
Analogue Out Max.
5.6 to 20.0 mA
Use this parameter to specify the upper current range
limit for the Analogue feedback. The current range
corresponds to the configured stroke range.
Note:
The current range limits can be freely configured
between 4 and 20 mA. However, the current range
must not be smaller than 10 % (1.6 mA).
Feedbk. Charact.
Direct, Reverse
Use this parameter to specify the characteristic curve
for the Analogue feedback.
-
Direct (rising) = Position 0 to 100 % = Signal 4 to
20 mA
-
Reverse (falling) = Position 0 to 100 % = Signal 20
to 4 mA
AO Alarm Mask
Alarm Maintenan.
Alarm OoSpec.
Alarm Check Fct.
Alarm Failure
When a general alarm is issued, an alarm current can
be sent via the Analogue position feedback. These
alarm groups are defined in accordance with Namur
NE107.
A high alarm current ( ‘High’ i >21 mA), low alarm
current (‘Low’ I < 3.6 mA, or ‘Off’ can be set for each
individual group.
AO Simulation
Off
Low
High
Input current
HW Alarm Current
The Analogue position feedback function is simulated
in this parameter group.
-
Off - Terminate simulation.
-
Reverse - Alarm current I < 3.6 mA
-
High - Alarm current I > 21 mA
-
Input current - The input current of the positioner
is output.
-
HW Alarm Current - The ‘AO Alarm Current’ set in
‘Service Mode’ is output.
Summary of Contents for SP8-10
Page 8: ...IM P707 01 CTLS Issue 1 8 SP8 10 Smart positioner Label example ...
Page 51: ...IM P707 01 CTLS Issue 1 51 SP8 10 Smart positioner Fig 28 Continued on next page ...
Page 52: ...IM P707 01 CTLS Issue 1 52 SP8 10 Smart positioner Fig 29 Continued on next page ...
Page 53: ...IM P707 01 CTLS Issue 1 53 SP8 10 Smart positioner Fig 30 ...
Page 86: ...IM P707 01 CTLS Issue 1 86 SP8 10 Smart positioner ...
Page 87: ...IM P707 01 CTLS Issue 1 87 SP8 10 Smart positioner ...
Page 88: ...IM P707 01 CTLS Issue 1 88 SP8 10 Smart positioner ...