IM-P707-01
CTLS Issue 1
58
SP8-10 Smart positioner
5.1.19 Range settings
Menu/parameter
Value range
Description
Upper Valve Rng
0.0 to 100.0 %
Normally, the valve range is determined automatically
during Auto Adjust.
A partial run of Auto Adjust that is limited to the control
parameters or valves and fittings without end stops,
however, requires manual adjustment of the valve
range.
Note:
If after automatic adjustment, the valve range is
manually rotated (old min. = new max. => old max.
= new min.) the device no longer reacts to set point
changes. A constant process value of 128 flashes on
the display.
Lower Valve Rng
0.0 0.0 to 100.0 %
Normally, the valve range is determined automatically
during Auto Adjust.
A partial run of Auto Adjust that is limited to the control
parameters or valves and fittings without end stops,
however, requires manual adjustment of the valve
range.
Note:
If after automatic adjustment, the valve range is
manually rotated (old min. = new max. => old max.
= new min.) the device no longer reacts to set point
changes. A constant process value of 128 flashes on
the display.
Upper Working Rng
0.0 to 100.0 %
The working range can be configured to be smaller
than the maximum mechanical working range.
The set point range always refers to the configured
working range. Use this parameter to specify the lower
limit of the working range.
Lower Working Rng
0.0 to 100.0 %
The working range can be configured to be smaller
than the maximum mechanical working range.
The set point range always refers to the configured
working range. Use this parameter to specify the upper
limit of the working range.
Summary of Contents for SP8-10
Page 8: ...IM P707 01 CTLS Issue 1 8 SP8 10 Smart positioner Label example ...
Page 51: ...IM P707 01 CTLS Issue 1 51 SP8 10 Smart positioner Fig 28 Continued on next page ...
Page 52: ...IM P707 01 CTLS Issue 1 52 SP8 10 Smart positioner Fig 29 Continued on next page ...
Page 53: ...IM P707 01 CTLS Issue 1 53 SP8 10 Smart positioner Fig 30 ...
Page 86: ...IM P707 01 CTLS Issue 1 86 SP8 10 Smart positioner ...
Page 87: ...IM P707 01 CTLS Issue 1 87 SP8 10 Smart positioner ...
Page 88: ...IM P707 01 CTLS Issue 1 88 SP8 10 Smart positioner ...