IM-P707-01
CTLS Issue 1
67
SP8-10 Smart positioner
5.1.26 Menu: Alarm output
Menu/parameter
Value range
Description
Alarm Logic
Active High, Active Low
Use this parameter to define the contact logic for
the alarm output.
-
Active High - > I > 2.1 mA
-
Active Low - > I < 1.2 mA
DO Alarm Mask
Alarm Maintenan., Alarm
OoSpec., Alarm Check
Fct., Alarm Failure
Use this parameter to select which general alarms
are output as an alarm current, depending on the
activated Namur classification group.
-
Alarm Maintenan. - Maintenance needed
-
Alarm OoSpec. - Operation outside
specifications
-
Alarm Check Fct. - Functional test needed
-
Alarm Failure - Errors
Alarm Simulation
Off, Low, High
The presence of an alarm can be simulated here
in order to output the alarm current.